8081_SITE PLAN-NEXTEL-AT AND T-PROVIN MT.-NORTH WEST ST. � �o� S` �� P1� - � T � T �ov�n �l� - I��-� wee+- 5t�� TowN OF AGAWAM INTEROFFICE QMP` MEMORANDUM To: Planning Board CC: John P. Stone, Clough Harbour & Associates, LLP, File From: Engineering Division Date: January 20, 2000 Subject: Site Plan - AT&T - Provin Mountain - North West Street - SP 295 Per your request dated January 14, 2000 we have reviewed the plans for the above mentioned subject entitled, " AT&T Wireless Services, Site I.D. # SP-38: Southwick Atop Provin Mountain Agawam, Massachusetts, for AT&T Wireless Services, by Clough Harbour & Associates LLP, dated January 12, 2000, scales 1" =120' and 1" = 10'." We have the following the comments: 1.) Calculations should be submitted to show that the tower and its foundation can structurally support the proposed additional antennas (9). The calculations should be stamped by a Massachusetts Professional Engineer. 2.) The street address should be included on the plans. 3.) The additional impervious area being created from the proposed concrete slab will create no substantial increase in run-off. It would be impractical to require detention to restore pre-construction stormwater events. 4.), Final approval will be based upon the Building Inspector's approval of zoning compliance. If you have any questions please do not hesitate to contact our division: Your truly, 11 NVanc f ones T. Daley, P.E. is Town Engineer Civil Engineer I h aengineerlsiteplanl sp295_03.wpd 0 TOWN OF AGAWAM 3S MAIN STREET -AGAWAM, VIASSACHUSETTS 01001 y Tel. 413-;88-0400 4M MEMO TO: Building Inspector, Engineering Dept., Police Dept., Fire Dept. FROM: Planning Board DATE: January 14, 2000 SUBJECT: Site Plan-AT&T -Provin Mountain-North West Street Please review and comment on the attached Site Plan for AT&T-on Provin Mountain, North West Street prior to the Board's January 20°i meeting. Thank you. DSD:prk • D C= N > n n Co C 3 0 3 n • _ D 4:� -emu rn .J r- . cn f AGAWAM FIRE DEPARTMENT O QP�VFNT a: 800 MAIN STREET • AGAWAM, MA 01001 TELEPHONE (413) 786-0657 1 4 4R Qd p M David A. Pisano Chief of Department FIRES 1/20/00 RE: Provin Mountain N. West ST. Wireless Communication Cell Tower Dear Sir; The Agawam Fire Dept. Has no objection to the proposed site additions. 1n your plans their is mention of a generator . Please note that any such equipment will most likely require permits from the Fire Dept., and a follow up inspection. Fire Insp.�M. Mercadante • oar J z • W W U U 2 I.Z� O1 W u °' z rn u z z� ?� Ja O O O N N r r M �•r:, coo � Z Ile r1 . Ll rQ �•t ; Drawing No. .-i _ �.. . • T-1 o TOWN OF AGAWAM 36 MAIN STREET 'AGAWAN1, MASSACHUSETTS 01001 y� Tel. 413-786-0400 O p�� �M MEMO TO: Building Inspector, Engineering Dept., Police Dept., Fire Dept. FROM: Planning Board DATE: January 14, 2000 SUBJECT: Site Plan-AT&T - Provin Mountain -North West Street Please review and comment on the attached Site Plan for AT&T.on Provin Mountain, North West Street prior to the Board's January 20'" meeting. Thank you. DSD:prk • i ANDERSON &KREIGIER 11,P Attorneys at Law STEPHEN D.ANDERSON The Bulfinch Building ACHESON H.CALLAGHAN Also admitted in Cr 47 Thorndike Street OfC ;Inxl Cambridge,MA 02141 DOUGLAS H.WILKINS ARTHUR P.KREIGER (617) 252-6575 orcuunul Also admitted in NY Fax: (617) 252-6899 RUTH H. SILMAN GEORGE A.HALL,JR. Also admitted in NH RACHEL GRAHAM EVANS January 14, 2000 BY MAIL Agawam Planning Board Office of Planning and Community Development 36 Main Street Agawam Massachusetts 01001 Re: Co-location on existing tower atop Provin Mountain Dear Sir or Madam: Enclosed are the following items in support of the request of AT&T Wireless PCS, LLC, for site plan approval for the collocation of 9 antennas on an existing tower atop Provin Mountain, 591 North West Street, in addition to an unmanned communications shelter at the site.- 1. Application for Site Plan Approval (Form D) 2. Ten copies of the Plans for this installation. Please place this matter on the Planning Board's agenda for the next available date. Based upon my prior discussion with your office, i understand that it is likely to be on the agenda for February 3, 2000. Please let me know if there are any additional questions prior to the meeting. Very Truly Yours, Do ]as H. Wilkins dwilkins _,andersonkreiger.com Enclosure cc: Joe Sweet (E-Mail:joe.sweet@attws.com) ;'; t Susan Johnson (E-Mail: susan.jolinson@attws.com) Wes Antwine (E-Mail: wes ley.antwine@crowncastle.com) w AMASawamSP381p1anbrd.001 �p►A _ t, ,D Printed on recycled paper AGAWAM PLANNING BOARD Form D Application for Site Plan Approval Please complete the following form and return it and 10 copies of the Site Plan to: Agawam Planning Board Office of Planning and Community Development 3 6 Main Street Agawam, MA 01001 1. Name of Business AT&T Wireless PCS, LLC Westwood, MA 02090. Address 2. Name of ApplicantIOWM AT&T wireless PCS , LLC , Lessee ue 11 Drive, suite IOU Address Westwood, MA 02090 Attention : Joe Sweet Telephone (781) 407-4520 cc : Stephen D. Anderson, Esq. 47 Thorndike Street 3. Name op`ingin n, rc1 teAger,- LLP Cambridge, MA 02141 Clough, Harbour & Associates � gpners Circle, Albany, NY 12205 Attn: Tony Mantello Telephone (518.) 453-45no 4. Please give a brief description of the proposed project: Collocate on an existing telecommunications tower. AWS proposes to attach 9 antennas to an existing tower and place an unmanned communications shelter atop Provin Mountain, 591 North West Street, Agawam, MA. Revised 11/06/98 1 y -t CLOUGH, HARBOUR -Q & ASSOCIATES LLP ENGINEERS,SURVEYORS. PLANNERS &LANDSCAPE ARCHITECTS ill WINNERS CIRCLE P.O. BOX 5269 ALBANY. NY 1 2 205-02 6 9 TEL: 51 8-453-4500 • FAX: 51 a-458-1 735 www.cloughharbour.com January 17, 2000� I Ms. Debra Dachos Director of Planning and Community Development 36 Main Street Agawam, MA. 01001 i Re:Boston & Providence MTA + Design Plan Submission. CHA FILE: 6655-01 —� Dear Ms. Dachas: We are enclosing Design Plans for the following site(s) as a Site L D. Site Name Number of Fri SP-38 Southwick 1 Should you have any questions or require additional information please contact me at(518)453-3953. Very truly yours, CLOUGH,HARBOUR & ASSOCIATES LLP ENGINEERS, SURVEYORS, PLANNERS & LANDSCAPE ARCHITECTS Ilk Anthony Mantello, P.E. .> rr"` Project Manager 100 ; . i �pN AWadb INS Enclosures (617)252.6575 W:1ATnBOSTOMCOKRFSMIiSIGMSUI,I,IVAMMARK-UP.WPP ~ Offices Throughout the Eastern United States "Satisfying Our Clients by Meeting Their Needs Through Dedicated People Committed to Total Quality." i i C a#_ 00 IOB LOGtt c� IoSSu�i BOX # I DOCUMENT# l0 PAGEk � � � rn rn CA [V N 5, m 6 m � a t- F- m a 0 F- ss S...E R v]. cli s Z A T& T W O U rn co SINN SITE INDS # SP cnl� Z_ 38M SOUTHVIICK Z O � W U C � W i In In 5 ° Q W ATOP PRO 'VIN IMOUNTAIN U a' 0 Y r W 0 c� � 0 V) T- A (; AW. AIM IMASSACHUSETTS = Q cca' rn I-- V) W .5 0 V) o y V) o w Q w >00 Q DRAWING NO. TITLE to a F- W p w IV z H j _ -0 U 74109e Rd Q — Q T-1 TITLE 0 Z�/ m 1�J = o o a A-1 VICINITY PLAN m -3 a d z A-2 SITE PLAN s 3 �D �' na uM O s �Qr {'w° " �r A-3 TOWER do ANTENNA DETAILS �_ - a �„ 0 L (Y A-4 MISCELLANEOUS DETAILS o � t E-1 ELECTRICAL SITE PLANS DIRECTIONS TO SITE: �fia a '�L — a TAKE THE MASS PIKE WEST TO EXIT 3. TAKE RIGHT ONTO �' 0 � E 2 ELECTRICAL DETAILS 202/20 SOUTH THROUGH WESTFIELD INTO SOUTHWICK. FOLLOW bin Dr �sC 0 N �° E-3 ELECTRICAL DETAILS 202/20 TO JCT 57 (FEEDINGS HILL ROAD). TAKE LEFT ONTO 3 p Q a CO LO 0 o RTE. 57 (EAST) - INTO AGAWAM. AFTER ENTERING AGAWAM TURN LEFT , ] .J z W N ONTO NORTH WEST STREET. FOLLOW NORTH WEST STREET TO RADIO STATION J Z SIGN ON LEFT TURN LEFT INTO DRIVE AND FOLLOW TO BACK OF BUILDING. � a c � Z . � O QUY � LATTICE TOWER LOCATED DOWN BEHIND RADIO STATION BUILDING. s m [1 fj o 00 Q ~ ° z } z } 00 North St Q PROLECT I Tanglewood Lane Z M O L CA nOw 3r Q _ Z U L. f Mountain � 0. � � W � z J C4w _j w UU U U rn Z �O LOCATION MAP U a SITE-_51ATIS11= NO SCALE A = u UNDERLYING LANDOWNER: ADAMS TV OF SPRINGFIELD INC. W J t ZONING DISTRICT: AGRICULTURAL 00 O a LATITUDE: N-42'05'01 .7" N CONSTRUCTION DOCUMENT APPROVAL DATE LONGITUDE: W-72.42'15.8"(GPS - NAD83) r GROUND ELEVATION AT Xi BASE OF TOWER: 627.9' (GPS — NGVD29) Q RF ENGINEER BY: TYPE SITE: EXISTING TOWER s;,.?`.;:. Z W , a 0 a 4 AT&T CONSTRUCTION COORDINATOR BY: JANUARY 12, 2000 SITE ACQUISITION COORDINATOR BY: CLOUGH. HARBOUR top Drawing No. H 14 & ASSOCIATES LLP I ENGINEERS, SURVEYORS, PLANNERS ERICSSON CONSTRUCTION/RBS: °�`o°�" T & LANDSCAPE ARCHITECTS Tel III WINNERS CIRCLE — ALBANY,, NEW YORK — 12205 a W P.O. BOX 5269 518--453-4500 Q UNDERLYING LANDOWNER BY: :sx:zs rn v � o � N o n in TRUE n g c� B15-1 N s 4 MN' c z 4 16-1 O 3 a � a �o 14' 0 2 5 a ,�0 1 z LANDS N/r BRUCE KERR, ETAL B.2071, P.292 B.7195, P.464 0 Cl 3-4SITE LANDS N11F CITY OF SPRINGRIELD 8.1792, P.483 f N -- cn N U TOWN OF AGAWAM 1 ASSESSORS MAP 814 Y W 0 v0 ..�PROPERTY LINE _ p IRON PIPE ►�] 2 a 0) y a z W '� o 0m QyVo .J w � Q � y Cuj j � +y Z Z J — —o h7 U? z W 2 O I 0 ' _Q) / I o 5 CO f Lv o F— 0 W u//1 EXISTING 13' ASPHALT 7 O O ACCESS ROAD 1-- LANDS NIP a RUBY E. LIGGET Q B.1693, P.573 j a QELLn 000 QJz _ ri EX TING GWYED TOWER f Q I Y i Lo m � a CE0 co QWIW �: In 2 'Q LL z z EXISTING BUILDING a / a W � 00 Q / E STING BUILDNG 00 EXISTING ASPHALT PARKING LOT Z o � - V � ° m Z � � Q Q x Q. GRAVEL �fL O U1 J v � Lu LANDS NAF 01 ,7 ADAMS TV OFSPRINGRELD, INC J2 _ _ e' B. 5574, P. 510 c� � LANDS N/J' a [� a4� MARK G. & J Z 0 JAMES BROWW -i 4 8.5685, P.318 u � v / EXISTING UILDING * SBg. r ul 150 w / 2C LOCATION Q c z EXISTING LATICE LAT.- 42-05-01.7 N O — TOWER LONQ 72-42-1& Mr 0 ELEV- 627.9 3 a 1 a SURVEY NOTES: �� PROPFRN IF-TTSA� 1. BASE MAPPING PREPARED BY CLOUGH, HARBOUR & ASSOCIATES LLP FROM A NOVEMBER 1999 FIELD SURVEY. O z 2. LATITUDE/LONGITUDE/ELEVATIONS WERE OBTAINED UTILIZING LANDS N/�' ° m a CODE BASED CPS REFERENCED TO NHDOT GPS BASE STATION. NOEL BROWN LATITUDE/LONGITUDE ARE REFERENCED TO NAD83 MASSACHUSETTS B.3508, P.291 '�tNoilvi Q MAINLAND ZONE. COORDINATES SHOWN, IF ANY, ARE EXPRESSED IN U.S. FEET, -� ELEVATIONS ARE REFERENCED TO NGVD 1929. TOP OF STRUCTURE HEIGHT AS SHOWN, IF ANY, DETERMINED BY VERTICAL ANGLE OR BY ACTUAL LOCATION, 3. FOR THIS PROJECT, CLOUGH, HARBOUR & ASSOCIATES LLP USED A TRIMBLE m PATHFINDER 8 CHANNEL PRO XL CPS SYSTEM. TRIMBLE TECHNICAL SPECIFICATIONS o \ o \ o \ STATE A HORIZONTAL DIFFERENTIALLY CORRECTED ACCURACY OF < 1 METER + 10ppm N c\v c\v P FOR THIS SYSTEM, CPS DIFFERENTIALLY CORRECTED VERTICAL ACCURACY IS GENERALLY 04 04 CONSIDERED TO BE 1 1/2 — 2 TIMES THE HORIZONTAL ACCURACY SPECIFICATION. ALL ACCURACIES ARE SITE DEPENDANT. THE ROOF ELEVATION SHOWN, IF ANY, WAS COMPUTED FROM CPS OBSERVATIONS, ALL OTHER ELEVATIONS WERE MEASURED ON SITE AND ARE In SITE RELATIVE, m v h C U a 4. NORTH ORIENTATION IS TRUE NORTH BASED ON CPS OBSERVATION. ,�/�fin NI PL N y MAGNETIC ORIENTATION IS BASED ON WEST SPRINGFIELD MASSACHUSETTS USGS QUAD SHEET. SCALE:. Q � •�,�� 1 AN z 5. UNDERGROUND UTILITIES SHOWN, IF ANY, FROM FIELD LOCATION ONLY. Drawing No. y 6. SUBJECT TO ANY STATE OF FACTS THAT AN ACCURATE BOUNDARY SURVEY WOULD DISCLOSE. PROPERTY LINES ARE ONLY SHOWN AS APPROXIMATE FROM TAX MAP AND DEED PLOT. GRAPHIC SCALE s 7. SUBJECT TO ANY STATE OF FACTS THAT AN UP--TO—DATE ABSTRACT OF TITLE WOULD 5 DISCLOSE. 120 ° °Q 1� 2� 4ao a 8. SUBJECT TO ALL RIGHTS, EASEMENTS, COVENANTS OR RESTRICTIONS OF RECORD. A_l W z 9. A BOUNDARY SURVEY WAS NOT PERFORMED BY CLOUGH, HARBOUR do IN FEET ASSOCIATES, LLP IN CONJUNCTION WITH THE PREPARATION OF THIS SITE. 1 inch — 120 it, s� 0 s 01/14/2040 12:23:33 GENERAL NOTES: v � RE SYSTEM__ SCHEDULE o "' 1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO EXAMINE ALL PLAN SHEETS AND 7, THE CONTRACTOR SHALL COMPLY WITH ALL REQUIRED PERMITS, MECH. SPECIFICATIONS AND COORDINATE HIS WORK WITH THE WORK OF ALL ANTENNA AZIMUTH MAU M 2 L IMA DQWNJLT RAD. CENTER, (AGL) �� CABLE SIZE A E9QX._CABLE LENGTH COLOR OTHER CONTRACTORS TO ENSURE THAT WORK PROGRESSION IS NOT 8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING, AND (ACTUAL �cn1r VARY)INTERRUPTED. INCURRING THE COST OF ALL REQUIRED PERMITS, INSPECTIONS, Rx1A 030 ALLGON AWS9016.02D NO 0' 1fi0 FT BOTTOM 1 5/8" 190 FT GREEN a � CERTIFICATES, ETC. 4 2. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING A NEAT AND TxA 030 ALLGON AWS9016,021) -- 0' 160 FT BOTTOM 1 5/8" 190 FT GREEN/GREEN ORDERLY SITE, YARD AND GROUNDS, REMOVE AND DISPOSE OFF SITE 9. THE CONTRACTOR SHALL PROTECT EXISTING PROPERTY LINE ALL RUBBISH, WASTE MATERIALS, LITTER, AND ALL FOREIGN SUBSTANCES. MONUMENTATION. ANY MONUMENTATION DISTURBED OR Rx2A 030 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT GREEN/GREEN/GREEN REMOVE PETRO-CHEMICAL SPILLS, STAINS AND OTHER FOREIGN DESTROYED, AS JUDGED BY THE OWNER OR OWNER'S REPRESENTATIVE RX1B 150 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE C _ DEPOSITS. RAKE GROUNDS TO A SMOOTH EVEN-TEXTURED SURFACE. SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE UNDER THE TxB 150 ALLGON AWS9016.02D -- 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE/BLUE ° C)SUPERVISION OF A LICENSED LAND SURVEYOR. 3. THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE- Rx2B 150 ALLGON AWS9016,02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE/BLUE/SLUE GROUND STRUCTURES AND/OR UTILITIES BELIEVED TO EXIST IN 10. ALL TRENCH EXCAVATION AND ANY REQUIRED SHEETING AND SHORING SHALL BE DONE RxiC 270 ALLGON AWS9016,021) NO 0' 160 FT BOTTOM 1 5/8" 190 FT WHITE THE WORKING AREA, EXACT LOCATION OF WHICH MAY VARY FROM IN ACCORDANCE OSHA REGULATIONS FOR CONSTRUCTION. THE LOCATIONS INDICATED, IN PARTICULAR, THE CONTRACTOR 11, CONTRACTOR SHALL BE RESPONSIBLE FOR DEWATERING AND THE MAINTENANCE OF TxC 270 ALLGON AWS9016.02D -- 0' 160 FT BOTTOM 1 5/8" 190 FT WHITE/WHITE IS WARNED THAT THE EXACT OR EVEN APPROXIMATE LOCATION OF SURFACE DRAINAGE DURING THE COURSE OF WORK. Rx2C 270 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT WHITE/WHITE/WHITE SUCH PIPELINES, SUBSURFACE STRUCTURES AND/OR UTILITIES IN THE AREA MAY BE SHOWN OR MAY NOT BE SHOWN; AND IT 16 dBI (14dBd) GAIN 90' HORIZONTAL -2' ELECTRICAL DOWNTILT TMA MODEL # N/A SHALL BE HIS RESPONSIBILITY TO PROCEED WITH GREAT CARE IN 12. ALL UTILITY WORK INVOLVING CONNECTIONS TO EXISTING SYSTEMS SHALL BE EXECUTING ANY WORK, 4 HOURS BEFORE YOU DIG, DRILL COORDINATED WITH THE OWNER OR OWNER'S REPRESENTATIVE AND THE UTILITY OWNER, BLAST, CALL 1-888-DIG-SAFE NOTIFY THE OWNER OR OWNERS REPRESENTATIVE AND THE UTILITY OWNER BEFORE EACH AND EVERY CONNECTION TO EXISTING SYSTEMS IS MADE, z_ 4. THE OWNER OR OWNER'S REPRESENTATIVE SHALL BE NOTIFIED IN WRITING OF ANY CONDITIONS THAT VARY FROM THOSE SHOWN ON THE PLANS. 13. MAINTAIN FLOW FOR ALL EXISTING UTILIT1ES. THE CONTRACTOR'S WORK SHALL NOT VARY FROM THE PLANS WITHOUT 14. ALL SITE FILL SHALL MEET SELECTED FILL STANDARDS AS DEFINED BY THE EXPRESSED APPROVAL OF THE OWNER OR OWNER'S REPRESENTATIVE, THE OWNER OR OWNER'S REPRESENTATIVE ON T#iE DRAWINGS. O 5. THE CONTRACTOR IS INSTRUCTED TO COOPERATE WITH ANY AND 15. CONTRACTOR TO GRADE ALL AREAS ON THE SITE TO PROVIDE POSITIVE DRAINAGE ALL OTHER CONTRACTORS PERFORMING WORK ON THIS JOB SITE AWAY FROM THE BUILDING AND THE TOWER. DURING THE PERFORMANCE OF THIS CONTRACT. � v) o z o 6. THE CONTRACTOR SHALL RESTORE ALL PUBLIC OR PRIVATE PROPERTY DAMAGED OR REMOVED TO AT LEAST AS GOOD OF CONDITION AS BEFORE DISTURBED AS DETERMINED BY THE OWNER OR OWNER'S "& \ REPRESENTATIVE. \ \ &u. ` 1636 W v0 \\ U LLJ O --INSTALL SYL r aWCE PRIA4 70 C0VS7RUCnov' 5 REMOVE AF7ER COIVSTRUCnAV HAS BEEN q_4 a) O COMPLETED _ ¢ Cc O) \ % \ INSTALL O V/A# L/NK Q Z W ' 0 (70 MA MH EXISANG �\ s O Z y O w / BaJARD �) LA-4 0 a Q N \ EXISTING PARKING LOT 10'X 20'A9 FAS EOU/PAIENr SIVR TOREA-4 2 3 < 'i \ \ AN A 11 'Y21COWCREV SXAe �''nV A-4 A-4 � Q 7L'1A LYEK B. A80W RN-W GRADE I W W ASPHALT INSTALL 6` or jW0 p?UwD CL < (A W O S7t7WE .SYJiPFAGL�' 77PEATJIIENr U} z = O POLE (Tn MA MY EXISANG) o N 4_0 15'f LONG CABLE 7RA Y AIOIUNTED GiV ¢ p � :3 In \ \� _,-�•�..� � / PACE SYlPPA'PTS A-4 _" — Q) X \ 22'-2" o / / Lil o 45 KW77CAL G10GU1?AL CABLE RUN A_3 a WOODS/ / aNMRUALr OF ANTENNAS 717 BE 1 3 \ POWER ✓ I- / PLACED A 160 AA' AV ENSANO A-3 A-3 CONa 162.7' LA771GE P rONE co _ L0 o IIn x2 CO C AD min O O TOWER HEIGHTS: � LL � ❑ N � 030 I / 1 �� TOP OF TOWER - 162.7 AGIL ] Z W I TOP PANEL - 147,6 AGL J z I- I rn GRAVEL TxC x I I CAB AY Rx1A I ' ' / DISH PANE 133.3 AGL AGL Q j Y I I (n\ DISH 2 - 10$,9 AGL m (1 O o0 I I Tx DDISH 3 ISH 4 - 12. A GIL (JI Q r , m J W \ I I Rx1C\ Rx DISH 5 - 91.7 AGL [X W w I EXISTING I ❑ 0- x I BUILDING I { _\ / / / Z Wu ono EXISTING ACCESS GATE ` I l J Rx18 \ / / / / .*+ (f] Z 0000 EXISTING GATE t I i TxS / / / / m o ` caNcfPAo Rx2S f O J Q z fI r� rn U] [ 150 I I LA 42-a � U) z = \ c oar \ \ x x I / / J z Llj Y. LLJ POLE \ - o r f / � WOODS ETrS b J / LLo o a � / waaos � / � Norrw POLE � r x 6'� N N N 1 m m � m U v SITE PLAN,- a SCALE; 1 - 10' O a U Drawing No. GRAPHIC SCALE 10 0 a 10 _ A-2 c IN FEET 1 inch - 10 ft uaviN,yrs55 01/14/2040 12:23:10 rn 1. GENERAL 6, CONCRETE (CONT.) d o A. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION H. UNLESS INDICATED OTHERWISE ON THE DRAWINGS, REINFORCEMENT SPLICES SAFETY, SHALL MEET CLASS B, TENSION LAP REQUIREMENTS IN ACCORDANCE WITH ALL PROVISIONS OF ACI 318 LATEST EDITION, UNLESS NOTED OTHERWISE. m B. CONTRACTOR SHALL DETERMINE EXACT LOCATION OF EXISTING UTILITIES a BEFORE COMMENCING WORK. HE AGREES TO BE FULLY RESPONSIBLE FOR ANY I, CURING COMPOUNDS SHALL CONFORM TO ASTM C-309, THESE DRAWINGS ARE BASED ON INFORMATION PROVIDED TO a AND ALL DAMAGES WHICH MIGHT BE OCCASIONED BY HIS FAILURE TO EXACTLY LOCATE AND PRESERVE UNDERGROUND UTILITIES, CLOUGH, HARBOUR & ASSOCIATES, LLP BY AT&T WIRELESS AND J. ADMIXTURES SHALL CONFORM To THE APPROPRIATE ASTM STANDARD As THE TOWER OWNER. AT&T WIRELESS AND THE TOWER OWNER C. INCORRECTLY FABRICATED, DAMAGED, OR OTHERWISE MISFITTING OR REFERENCED IN ACI-301, a o NONCONFORMING MATERIALS OR CONDITIONS SHALL BE REPORTED TO THE OWNER ASSUME ALL LIABILITY FOR ALL STRUCTURAL ANALYSIS, INTEGRITY PRIOR TO REMEDIAL OR CORRECTIVE ACTION, ANY SUCH ACTION SHALL K. DO NOT WELD OR TACKWELD REINFORCING STEEL. L. ALL DOWELS ANCHOR BOLTS, EMBEDDED STEEL, ELECTRICAL CONDUITS, PIPE AND REQUIRED IMPROVEMENTS OF AND TO THE EXISTING TOWER, REQUIRE APPROVAL, EXISTING STRUCTURES, AND EXISTING SUPPORTS. SLEEVES, PIPING, WATERSTOPS, INSERTS, GROUNDS AND ALL OTHER EMBEDDED D. EACH CONTRACTOR SHALL COOPERATE WITH THE OWNER'S REPRESENTATIVE, AND ITEMS AND FORMED DETAILS SHALL BE IN PLACE BEFORE START OF CONCRETE COORDINATE HIS WORK WITH THE WORK OF OTHERS. PLACEMENT, E. PAINT ALL ANTENNAS, MOUNTING HARDWARE, CABLES, CABLE TRAYS, ETC. TO MATCH M. LOCATE ADDITIONAL CONSTRUCTION JOINTS REQUIRED TO FACILITATE EXISTING STRUCTURE PER OWNER REQUIREMENTS. OWNER SHALL APPROVE COLOR, CONSTRUCTION AS ACCEPTABLE TO ENGINEER, PLACE REINFORCEMENT CONTINUOUSLY THROUGH JOINT. F. ALL DAMAGED, MARRED, SCRAPED, ABRADED, ETC. AREAS OF EXISTING PAINT SHALL BE N. REINFORCEMENT SHALL BE COLD BENT WHENEVER BENDING IS REQUIRED, z REPAIRED PER OWNERS REQUIREMENTS. OWNER SHALL APPROVE COLOR. I I 0, PLACE CONCRETE IN A UNIFORM MANNER TO PREVENT THE FORMATION OF COLD II I o 2. DESIGN LOADS JOINTS AND OTHER PLANES OF WEAKNESS. VIBRATE THE CONCRETE TO FULLY A. WIND LOADS: PER THE STATE BUILDING CODE EMBED REINFORCING, DO NOT USE VIBRATORS TO TRANSPORT CONCRETE THROUGH B. PRESUMPTIVE BEARING CAPACITY: 2000 PSF CHUTES OR FORMWORK. (VERIFY SOIL BEARING CAPACITY WITH GEOTECHNICAL ENGINEERS REPORT) CENTERLINE OF ANTENNAS TO BE C. PREFABRICATED BUILDING: 40,000 LBS P. DO NOT PLACE CONCRETE IN WATER, ICE, OR ON FROZEN GROUND. D. ROOF UNIFORM SNOW LOAD: 40 PSF PLACED AT 160' AGL ON EXISTING N � (DRIFTED SNOW AS PER THE STATE BUILDING CODE,) 0. DO NOT ALLOW CONCRETE SUBBASE TO FREEZE DURING CONCRETE CURING AND 1fi3' LATTICE TOWER o SETTING PERIOD, OR FOR A MINIMUM OF 14 DAYS AFTER PLACEMENT. II.I II " 3. EXCAVATIONS/FOUNDATIONI EXISTING PANEL ANTENNAS ® 146' AGL A. FOUNDATION EXCAVATION SHALL BE HAND-TRIMMED TO REMOVE LOOSE R. FOR COLD--WEATHER AND HOT-WEATHER CONCRETE PLACEMENT, CONFORM TO MATERIALS. APPLICABLE ACI CODES AND RECOMMENDATIONS, IN EITHER CASE, MATERIALS CONTAINING CHLORIDE, CALCIUM, SALTS, ETC. SHALL NOT BE USED. PROTECT FRESH CONCRETE FROM WEATHER FOR 7 DAYS MINIMUM, cn W B. EXTERIOR FOUNDATION BACKFILL SHALL BE SELECTED GRANULAR FILL, Y tt- V) O U_ uj --I CDC, DO NOT PLACE FOOTINGS IN WATER OR ON FROZEN GROUND. V) Q EXISTING 6' DISH 0 133.3' AGL p D. SOIL BEARING SURFACES, PREVIOUSLY ACCEPTED BY GEOTECHNICAL ENGINEER, s�o� 030' j .Q) p) WHICH ARE ALLOWED TO BECOME SATURATED, FROZEN OR DISTURBED SHALL BE Q [] W O REWORKED TO SATISFACTION OF GEOTECHNICAL ENGINEER. O m Q y (no E. DO NOT ALLOW GROUND BENEATH FOOTINGS TO FREEZE, m Z M F. FOOTING EXCAVATIONS SHALL BE CUT NEAT. s�OM a LEI •� G. ALL STRUCTURAL BACKFILL AND SUBBASE UNDER SLABS-ON-GRADE AND FOOTINGS ANTENNA MOUNTING PIPE SHALL BE "SW" OR BETTER PER ASTM D-2487 COMPACTED TO A MINIMUM 959 BY MICROFLECT PART N0, I z Q J -- -6 STANDARD PROCTOR DENSITY PER ASTM D-698. B1478 W = °o H. SUBGRADE BELOW SLAB-ON-GRADE SHALL BE REVIEWED AND ACCEPTED BY TRUE ® EXISTIVG 8' DISH 0 112' AGL EXISTING 6' DISH 0 108.9' AGL o GEOTECHNICAL ENGINEER BEFORE CONCRETE SLAB PLACEMENT. N z � 4, ANTENNA SUPPORT BRACKET NOTES N z W 50 3 m A. DESIGN RESPONSIBILITY OF ANTENNA MOUNTING BRACKETS AND POLES AND ALL , z I-- a O O COMPONENTS THERE OF AND ATTACHMENT THERE TO SHALL BE THE RESPONSIBILITY 270' ----- 6 < °- F_ O OF THE MANUFACTURER. MFR SHALL PROVIDE TO THE ENGINEER FOR APPROVAL, 14 � o �- co F- DRAWINGS DETAILING ALL COMPONENTS OF THE ASSEMBLY, INCLUDING CONNECTIONS, ® a ¢ DESIGN LOADS, AND ALL OTHER PERTINENT DATA. a o STANDOFF FRAME BY B. BRACKETS SHALL BE DESIGNED TO SUPPORT CURRENT AND FUTURE PANEL ANTENNAS MICROFLECT (PART NO. z z AND COAXIAL CABLES AS SHOWN. 99560) OR EQUAL EXISTING 4' DISH 0 91.7' AGL EXISTING DISH 8' 0 92,6' AGL z w 5. STRUCTURAL STEEL NOTES 150• o Q a L 0 0 A. STRUCTURAL STEEL SHALL CONFORM TO THE LATEST EDITION OF THE AISC "SPECIFICATION Cl- J Z W N j FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS , 1 °a 0 .,J Z I Y B. STEEL ANGLES, BASE PLATES, BEARING PLATES AND MISC. FABRICATION SHALL BE MADE ANTENNA Q U I FROM STEEL MEETING THE REQUIREMENTS OF ASTM--A36 WITH A MINIMUM YIELD STRESS _ NO SCALE Q- O co OF 36 KSI, ALL STEEL TUBES AND PIPES SHALL BE A500 STEEL MINIMUM. EXISTING 163' LATTICE TOWER Lu u Q r C. ALL INTERIOR STRUCTURAL STEEL SHALL BE, WHEN DELIVERED, FINISHED WITH ONE COAT L E W w Ln FABRICATOR'S NON-LEAD RED OXIDE PRIMER, PRIMING SHALL BE PERFORMED AFTER Q >_ Q z SHOP FABRICATION TO THE GREATEST EXTENT POSSIBLE, ALL DINGS, SCRAPES, MARS, Wu AND WELDS IN THE FINISHED AREAS SHALL BE REPAIRED BY FIELD TOUCH-UP PRIOR z TO COMPLETION OF THE WORK, Q❑ D. ALL EXTERIOR STRUCTURAL STEEL SHALL BE, WHEN DELIVERED, HOT-DIP GALVANIZED MICROFLECT PART #B251 �R [l Z m z ACCORDING TO ASTM A123. TOUCH-UP FIELD WELDS AND ABRADED AREAS W/2 COATS COMBINATION SQUARE .L 0 W J Q OF GALVANIZED PAINT. RAIL �1� In W 1 %_ E. DO NOT PLACE HOLES THROUGH STRUCTURAL STEEL MEMBERS EXCEPT AS SHOWN AND V �JJ DETAILED ON STRUCTURAL DRAWINGS, Z_ z F, CONNECTIONS: Q L'J 1, ALL WELDING SHALL BE DONE BY A CERTIFIED WELDER USING E70XX ELECTRODES J W AND WELDING SHALL CONFORM TO AISC AND AWS D1,1. WHERE FILLET WELD SIZES U v ARE NOT SHOWN, PROVIDE THE MINIMUM SIZE PER TABLE J2.4 IN THE AISC "MANUAL OF STEEL CONSTRUCTION ", 9TH EDITION, AT THE COMPLETION OF WELDING, ALL v DAMAGE TO GALVANIZED COATING SHALL BE REPAIRED. cn 2. MINIMUM CAPACITY OF CONNECTIONS: FOR CONNECTIONS NOT DETAILED, w PROVIDE CONNECTION CAPACITY OF AT LEAST THAT REQUIRED BY PART 2 OF THE T z AISC MANUAL (9TH EDITION) IN THE SECTION "ALLOWABLE LOADS ON BEAMS", FOR ■i z_ THE GIVEN MEMBER AND STEEL SPECIFICATIONS, CONCENTRATED LOADS NEAR SUPPORTS MUST. BE ADDED. U a - N 5' t LONG CABLE TRAY MOUNTED ON Q 3. CONNECTION DESIGN BY FABRICATOR WILL BE SUBJECT TO REVIEW AND APPROVAL POLE SUPPORTS. 4. BOLTED CONNECTIONS SHALL USE BEARING TYPE GALVANIZED ASTM A325 BOLTS (3/4" DIA.) AND SHALL HAVE A MINIMUM OF TWO BOLTS UNLESS NOTED OTHERWISE. 10' X 20' PREFAB EQUIPMENT SHELTER 5. NON-STRUCTURAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8" DIA. GALVANIZED ASTM MICROFLECT PART #8291 ON A 11' X 21' CONCRETE SLAB WITH CROSS PIECE 40" LONG TOP ELEV. = 6" ABOVE FINISH GRADE etr A307 BOLTS UNLESS NOTED OTHERWISE. GALV VERTICAL SPACING pG 6�3 NU S 6. CONCRETE PER MFR RECOMMENDATIONS EXISTING EQUIPMENT BUILDING A. DESIGN AND CONSTRUCTION OF ALL CONCRETE ELEMENTS SHALL CONFORM TO INSTALL B' HIGH CHAIN �, z THE LATEST EDITIONS OF THE FOLLOWING APPLICABLE CODES: ACI 301 LINK FENCE WITH BARBED "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS"; ACI 318, EXISTING CHAIN LINK FENCE WIRE (TO MATCH EXISTING) X "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE"; �''�Orrvr e X x B. MIX DESIGN SHALL BE APPROVED BY OWNER'S REPRESENTATIVE PRIOR TO PLACING CONCRETE, C. CONCRETE SHALL BE NORMAL WEIGHT, 6% AIR ENTRAINED (f1,57.) WITH A MAXIMUM rn rn rn 4" SLUMP, AND HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 4000 PSI a o a UNLESS OTHERWISE NOTED. n N cv D. MAXIMUM AGGREGATE SIZE SHALL BE 1". -- 1 �I I� --I——II►L�— I --—�—I-�--C_—�I - M THE FOLLOWING MATERIALS SHALL BE USED: E. 1=I I1 1I cn PORTLAND CEMENT: ASTM C 150, TYPE 1 , m m I REINFORCEMENT: ASTM A 185 NORMAL WEIGHT AGGREGATE: ASTM C 33 WATER: DRINKABLE o 0 ADMIXTURES: NON—CHLORIDE CONTAINING Drawing No. CID F. REINFORCING SHALL CONFORM TO ASTM A-615 WITH SUPPLEMENT, MINIMUM 3 YIELD STRENGTH Fy = 60 KSI. REINFORCING DETAILS SHALL BE IN NO SCALE ACCORDANCE WITH THE LATEST EDITION OF ACI 315. 2 CABLE SUPPORT ON ANTENNA TOWER — G. CONCRETE COVER AROUND REINFORCING BARS (U.N.O.) SHALL BE: _ NO SCALE NOTES 1. CONTRACTOR SHALL COORDINATE EXACT ANTENNA ATTACHMENT. ■ri■ 1. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED EARTH,,,,,,..3" NOTE: CONTRACTOR SHALL VERIFY CABLE MOUNTING W/STRUCTURAL 2, ANTENNAS TO BE INSTALLED WITH DOWNTILT BRACKETS. A3 2. CONCRETE EXPOSED TO EARTH, WEATHER.........................2" 3, SLABS....................................................3/4 ANALYSIS RECOMMENDATIONS. 4. ALL OTHER CONCRETE.....................................1 1/2" .,,,; n ,r.,ss a1/14/2040 1z:xz:cs o� v � o � N S, m v � n F— a a s, m c = 6" o p (TYP) CONC CAP 34" DIA. 40 STEEL J ANCHOR BOLTS N PIPE!FILLEDCID W/LEAN CONC (TYP) Ln 11'x21' CONCCD i SLAB z I � SHELTER 1/4 BASE FRAME is BM FLANGE PL 12"x12» 1/2" EXPANSION 3" 6" FILLER do SEALANT I I v ~Ln z o U •Ln U T/STL T/CONC SHELTER PLATE (TYP) RING I SLAB ,.� (TYP) SEE \ \\\\\� v c o \\\\\\\ 10'x20' SHELTER ANCHOR BOLT 2 �/ 2' SQ. CONCRETE PAD W� O TYP /��// /��� B" SUBBASE 2 O Q d7 / a . a \\/\ UNDER CONC PAD. can �-- •— O TYP 3/16__7_W \�/� ;"'4 .�� D < W W N g'-6" 8'-6" 1'-6" (TMP) 2KANN PLAIE DETAIL a (n N NO SCALE co 0 O .L > po a L<, W o , NOTE: CONTRACTOR SHALL VERIFY SHELTER BASE , a FRAME CONSTRUCTION PRIOR TO WELDING 'r 4 . ¢ Q J ._ -O TO BEARING PLATES, -J W 2 p . ' • ° ' CONC BASE 1 .4 • ` (3000 PSI CONC) o W — NO SCALE •.. as -Al �. � Z U � � U} 5 V) Fn Q) LJ O IL ro ~ h a Q a 1W Dix QQM � o °o � J LHu N � 6 BOLLARD DETAIL W J z w , NO SCALE D j LJ mu CI000 � W � W 3: U-' FENCE CAP Q W Q 2 — > (L Z c. CABLE TRAY El < z° GRIP STRUT 0 J Q ~; d 3/8" DIA THREADED ROD � i Q SNAP--IN HANGER FOR "" z = COAX CABLE (TYP) Q a � z 3 ROWS OF GALV ...1 W P1000 UNISTRUT v 3" DIA SCH 40 v PROPOSED SHELTER PIPE COLUMN FOR j< p WAVEGUIDE SUPPORT 1" CHAMFER #4012" EW u cn w z U (TYP ALL SIDES} 6" CONCRETE SLAB 6" EXPOSED Q CONCRETE u 2" CLR CONCRETE PIPE BASE 2x4 STAKE 5' O.C. EXISTING AND PROPOSED FINISH GRADE mil POLY ON W` f/j /\/ //\/ ' °o°Ooa°ao°o°°aa°°oa°"afl°"oa°"oQ°°o°"°o°"`yo° '°°�''o°"�oa�,no°�, UNDISTURBED SUBGRADE FINISHED GRADE a \\\�j/\/\\/\\ 3� ° a o °ap ao° °ao po° ooa aaa o°° o°°oo°°oop°oa° °o STAPLE THROUGH NYLON P�,��y �rrSb� U 'Y\� /\ °b0 obOOd00�1°aaa°°b°° °°°°b°°b°b°°a°°aa°°aa°°a°°°°°°°a°°a° N //�\//\ o o °o b °a bo 00 00 ob° oa° b°° o0 ooaabooa°aa° WASHER. 2 PER STAKE TRENCH, LAY FABRICSUPAC OR I j��j\� » FABRIC MIRAFI FILTER o \ AND a N /\\�\ \\ \\ \�\�\ \ \\�Y\\/\\/\\/\\/�' . \\�\�/V \\/\ r� C MNO�Y Q EXISTING GROUND 6" CRUSHED STONE (MIN.) — — —II — 6» II---IIII—I II—II X alp =� I i=1 11=1 I I ��•;� N•� 1=1 I I 1 I 1=1�1=1 11=1 11= UNDISTURBED SUBGRADE (BEDROCK OR I �=1 I I=III III I III , ,I �,;,III;,� I �,;,I P- STRUCTURAL FILL) 4 2'-0" WIRE STAPLE 37SHELTER SLAB DETAIL " m m — NO SCALE 1 --0 DIA m _0 v , NOTES: 1. PROVIDE CORNER BARS AT EACH CORNER OF PAD. o o u BAR SIZE SHALL MATCH HORIZONTAL REINF. 'i Drawing No, 2. COORDINATE LOCATION OF UTILITY PENETRATION THRU 4 CA13LE TRAYPOLE SUPPORT 5 5ILT, DETAIL N SHELTER SLAB WITH ELECTRICAL DRAWINGS. — NO SCALE — NO SCALE 3. CONTRACTOR SHALL WATER STOP ALL CONDUIT NOTE: ICE BRIDGE SHALL SPAN NO MORE THAN 6'-0" PENETRATIONS THRU SLAB AND SHELTER. BETWEEN SUPPORTS. A 4 4. COORDINATE SLAB PLAN W/ SHELTER MFR. Z A L9V lf`IgY.4$$ ���T��zQ4� �Z:�.z:�•r O 0 'RUE WnUT_Y CONTACTS: LEGEND WESTERN MASS E_ECTRIC CO. m �" • RICK RIZZLIE — -- — — — UNDERGROUND CONDUIT (413) 785--5871 Q - #2 AWG GROUNDING CONDUCTOR do r "�-a.�- • 3 �) METER o 1 E--2 TYP. GROUND BAR Li 2 � r f a 5/8" x 10'--0" COPPER CLAD GROUND ROD. MINIMUM SPACING 10 -0 • I J r MAXIMUM SPACING 15'-0" 1 � EXISTING METALLIC FENCE & NEW N t fr O INDICATES CODED NOTE NUMBER z r r Q R ' 12 1 DETAIL NUMBER Q I AT&T__P_REFAB -r E-2 DRAWING NUMBER LOCATION z o EQUIPMENT r 1 SHELTER . 1 c o r r N U) 0 r 5 1 GENERAL—NOTES I i E_2 1. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM CONDUCTORS SHALL NOT BE USED. 1 12 6 1 ` 2. CAP ALL EMPTY CONDUITS AT BOTH ENDS. SEAL ALL CONDUITS WITH PULL CORDS & W 1 E-3 + CONDUITS WITH GROUND WIRES. Y O + 3. COORDINATE ALL PENETRATION LOCATIONS WITH ACTUAL BUILDING PLANS. U_ V) j 4. DRAWINGS WERE COMPLETED BEFORE UTILITIES COULD CONFIRM SOURCE OF SERVICES. v Z 00 + r DRAWINGS ARE BASED UPON SITE OBSERVATIONS ONLY. < J -+-+ 0) W '� r r r c„ — o CONC PAD O LLJ r _ �-�- + E-3 TYP. `; E-3 TYP 00 M c .. �...- - ' W o Q j -0 O :2 CABLE TRAY �� �� �� L J 0 LLJ 0 0- 7 E_3 x Q ac a. CE � N LO 8 E�3 � J Z W N � TYP. D j Q I Y n � � _j L] O�F� I (1 00 CO QW ulW Ln 3 ENLARGED-EQUIPMENT 6R A - GROUNDING PLAN z SCALE: 3/8" a 1'-0" Q W U O 00 Q00 00 0 Ulz m 0 11 A O �� Q Wj _ ] W � z 0 < 0 Q z / J ` � W Uu +~_ U x 2 - - -2 � .� w 3: acn U " • 13 E�3 1 - `r� _� • CODED -NOTES 1 • 0 n 1 4" C. w/(3) 600 KCM. X 1 0 2"C/ w/(3) #4/0 + #6G TO BUILDING DISTRIBUTION SYSTEM. COORDINATE • 0 H" EtrS 2 EXACT TTEERMINATION LOCATION WITH OWNER. N O 4 TELEPHONE CONDUIT WITH PULL WIRE. � TELEPHONE SERVICE ENTRANCE. PROVIDE 4" CONDUIT w/ PULL WIRE CONC W/ 2 Y TO BUILDING TELEPHONE BACKBOARD. COORDINATE EXACT TERMINATION 1 gMT PREFAB LOCATION WITH OWNER, GENERATOR )EQUIPMENT �o►rr,r Q �5 EXTERIOR GROUND RING. ! SHELTER O BUILDING MOUNTED GROUND BAR. CONC 2 O7 TOWER MOUNTED GROUND BAR. a ANTENNA GROUND BAR. , O9 CONNECTION FROM EXTERIOR GROUND RING TO INTERIOR HALO. ~"+ 10 CONNECT TO EXISTING EXTERIOR GROUND RING. LOCATE IN FIELD. m x CONC PAD m 11 EXISTING UTILITY POLE WITH ELECTRIC AND TELEPHONE SERVICES x m m # Q N FOR AT&T. c� r 12 HVAC UNIT. � o V 13 Drawing No. NEW 400A, 120/24OV, 10 SQUARE "D" METER-PAK METER CENTER w/ OD M 2 METERS. (1) 200A METER SOCKET/CB FOR AT&T AND (1) 200A MEITER SOCKET/CB FOR FUTURE. METER BY UTILITY, X c Ly PARTIAL SITE - POWER & TELEPHONE LM E- z SCALE: 1/4" - 1'-0" W J v iv' !4nyre55 07/14/Z040 12.21.46 Q' o' oo 43 r S; a7 TIE INTO EXISTING TIE INTO EXISTING EXTERIOR GROUND RING EXTERIOR GROUND RING a u C-) LOCATE IN FIELD LOCATE IN FIELD r m 0 0 a ¢ Q o � � I I cn I EXTERIOR GROUND RING L—WITH GROUND RODS AS INDICATED ON GROUNDING PLAN I UNDERGROUND UTILITY z —rr— rlrr-- --r--- r—■.r—.r.rrrw+w„ r.—w...-- rr am+r —.w�.------ J----- ------w ------r—rrJ------------- 1 f I I I j BACKFILI. WARNING CAPE I i i i i I I i SEE NOTE FINISHED GRADE I I I I I I I I I o�i 00 I I I I I I TOWER GROUND BAR INTERIOR HALO I HVAC TELEPHONE I EFENCE POST EXISTING CABLE TRAY \' 4 PLACES I EQUIPMENT LAC SERVICE SERVICE I P, CORNERS FENCE �cSUPPORTS I I `n TYP. 2 TYP. 2 I I o TELECOMMUNICATION CABLE TRAY 1 0 Q CABLE SHEATH 1 .{ ;. SAW CUT EDGE EACH w SIDE (IF REQUIRED) I I I :' ; ; :;r=:t•::,•- =: ONE OR TWO CONDUITS N z I I 3" SAND ENVELOPE r' o u' c" I I I CONDUIT DING AS REQUIRED, SEE SITE PLANS. i 3" BUILDING GROUND BAR I MASTER GROUND BAR ANTENNA GROUND BAR (TYP. OF 3) 11 I I NOTE, REPLACE EXISTING SURFACE CONDITIONS IN KIND TO INCLUDE, W I BUT NOT LIMITED TO: CONCRETE, CRUSHED STONE, SELECT Y h O GRAVEL, ASPHALT CONCRETE, TOPSOIL AND GRASS. TELECOMMUNICATION C BLE TRAY U ~ O CABLE SHEATH CABLE TRAY 1 PLACE ANTENNA TELECOMMUNICATION [CABLE TRAY _ FRAME 11 CABLE SHEATH � � -� � E2 UNDERGROUND CONDUITS W O — NO SCALE O m. Lil o Q w DEL CONNECTION TYPE TO EQUIPMENT AND GROUND BARS SHALL BE COORDINATED WITH EQUIPMENT MANUFACTURER AND OWNER. ' • a J > M •— a Q YI LEGEND m Z W = 0 5/8" x 10'-0" COPPER CLAD GROUND ROD, 5 0 Ljj Q) ------- #2 AWG BARE SOLID TINNED COPPER GROUND WIRE. z w 3 -- - #6 AWG BARE SOLID TINNED COPPER GROUND WIRE, LJJ O i— a O GROUND BAR U} o 4 ----- — #4/0 AWG FLEXIBLE COPPER BRAID Q 1 SCHEMATIC DIAGRAM — GROUNDING SYSTEM NO SCALE (I EL Ul m 0 0 cr �-- N co ] JZW N I ❑ J Q '= � ai JUY � W lflQ r Lc) ° Q z UTILITY POLE Q W U � , z 00 I ' o BARBED WIRE CRIMP-ON CONNECTOR U ❑ Q o TO EACH STRAND (TYP.) ❑ Ul ZZ m z Ul J Q HEAVY DUTY EXOTHERMIC ti o TOP RAIL WELD L u a 2 2 � (nZ = FENCE FABRIC NOTES (4 Z W _j 1, BOND ALL METAL OBJECTS TO POLE GROUNDING SYSTEM, U 2. COORDINATE ALL INSTALLATIONS TO UTILITY POLE WITH UTILITY COMPANY. U POLE CODED NOTES Ir 4 CONDUCTORS FROM UTILITY POLE TO METER INSTALLED BY CONTRACTOR. ICONTRACTOR Lj TO PROVIDE SUFFICIENT CABLE TO REACH A MINIMUM OF 24" O " ABOVE TERMINATION LOCATIONS, AND ROUTE TO SERVICE DISCONNECT WITH- a a OUT A SPLICE a o z O PROVIDE INSULATING BUSHING, USE DUCT SEAL TO MAKE WATERTIGHT. 3� PIPE STRAPS, INSTALL AT NOT MORE THAN 2'-0" INTERVALS, OTELEPHONE SERVICE CONDUIT WITH PULL CORD. SEE SITE PLAN FOR CONDUIT NU ETTS d SIZE & ROUTING, �Pp FENCE POST SOLID TINNED GROUND r WIRE FINISHED O SWEEPS MUST BE MADE USING RIGID GALVANIZED STEEL CONDUITS, LL 4 ° GRADE—1 o a D ca r'� i;• � P�k. TENSION WIRE g ff.• 1 HEAVY DUTY EXOTHERMIC WELD I WITH CORROSION PROTECTION `~ o o o ' '• EXTERIOR GROUND RING 5 ..rr• ' N CV N F . TO EQUIPMENT SEE ELECTRICAL, PLAN $ i FOR CONTINUATION 30" OR 6" BELOW FROST LINE cn i i a m 4 SERVICE POLE �- POWER & TELEPHONE 1 3 FENCE GROUNDING _ No SCALEU — NO SCALE Drawing No. � c a rn r m E-2 W Z C] a .sv+dY ,Ss Q1l1til204� 12:21:1F - O T II] a C a U 1'-6" m 1" _1-1/2" TYP. TYP, TYP. 3/4" � � 100 1-1 2" TYP, TYP, TYP, � I I I 7/16*0 HOLE (42) 01 O00 R 7 16.0 HOLE I i N � 00 + 000000000- - u I I / Ec16) 00000000000000- - + - 660 00 00-- _00000000 �o 00 0 0 0 �- + r 2 , - 0000000 _ 7/16"0 MOUNTING HOLE 2 00 7/16"0 MOUNTING HOLE 1 (2) 1 (2) 3 O 3 0 w cn SIDE MEW P_L..A N V I Ems[ o Ca 51DE VIEW Q L A„ N _ V� I , E W N o O #R415DA4 INSULATOR a #WBKT1 WALL BRACKET O #GB11441BERMG6 O #R4150A4 INSULATOR O #WBKTt WALL BRACKET O #GBI14212ERSG8 YI 1 GROUND BAR ASSEMBLY W NO SCALE 2 GROUND BAR ASSEMBLY (SECTOR) v W (j o NO SCALE 0 NOTE: 1. ALL PARTS REFERENCED MANUFACTURED BY HARGER LIGHTNING PROTECTION, INC. = a .�_I +) m NQ� 1. ALL PARTS REFERENCED MANUFACTURED BY HARGER LIGHTNING PROTECTION, INC. I— � V) - W '� o O Ld Ld y � O a N N > Q 0�0 0 Q �} Q Zc) W - -0 = 0 5 U 3 � J Q) 5 LLJ — N LLI 0 U' 0 HEAVY DUTY EXOTHERMIC a F. WELD oc FENCE POST — SOLID TINNED GROUND WIRE N Io J TENSION WIRE W N � J z W Q rz tn HEAVY DUTY EXOTHERMIC WELD a U p I WITH CORROSION PROTECTION m Q r co -f•' EXTERIOR GROUND RING W w a a } < z _ - > 00 30" OR 6" BELOW FROST LINE EXTERIOR SHELTER Er z ao WALL " U �] � m � J 3 EXISTING FENCE -- GROUNDING Q Q �- NO SCALE � W O a` � uJz oa0 O .J z A A SQUARE (4 LiJ U D it METER- U PAK MP42200 C) rT � L >- CW 8 Bo = od � Z GRADE V z z� GROUND RING a = 0 ---------- HEAVY DUTY ETS EXOTHERMIC �P�� & u WELD a GR DEED �M o �orvw �C 30" OR 6" BELOW FROST LINE v = 2"C. PVC TO AT&T o n n n PRE-FAB SHELTER 4" PVC FROM UTILITY 4 COPPER--CLAD STEEL a 0 m v NO CALF ROD 5 METER BANK...- NATION � p y , NO SCALE T Q U v' w U ° 1 t M O 0 U W I Drawing No. m M n W m W a z a v.virfs{.r.,55 Ot/14/204fl '12:27:E12 rn rn a \ a rr3 [y r Q `3 TRUE a Cl) B15-1 N im 16-1 4 MN � oa 0 3 14• 5 2 o � 0 V) LANDS N10 r" BRUCE KERR, ETAL B.2071, P.292 I B.7195, P.464 0 C13-4 SITE LANDS NIF CITY OF SPRINGFIELD B.1792, P.483 j N -- a TOWN OF AGAWAM I /� ASSESSORS MAP 814 r` V' W o PROPERnr UNE v � � O IRON PIPE N it -4--, Q r � � zW � cy —� w o E� CIO . . 3 CL y > Q ro - 1 00 < y-• y L 2 co M < F- W n Cl. a _z J •_ 0 t t cn Z U W = o / tAl Q) -3 5 � m LLJ O r�W H a O 494 EXISTING 43' ASPHALT z (!� O ACCESS ROAD N4 LANDS N/Y o RUBY E. LIGGET Q a a 1693, P.573 � a \ G / 0 \. r coUl Ul 0 0 r � a EL N Lo � J Lu zwN � y EX TING GUYED TOWER I D J Q Ln I Y Ln I W 0 00 � W W � In J2 `Q EXISTING BUILDING l� w r -- Q Z 00 E STING BUILDING [(� z c00o � EXISTING ASPHALT PARKING LOT r ❑ Q p Z m Z U 4� GRAVEL WE J m CL ADAMS TV OFDSPR NI MELD, INC J2 U z < 8' B. 5574, P. 510 LANDS N/!:' 0Q [] MARK G. & Z W Io JAMES BROWN J W v 0 I4� B.5685, P.318 U U EXISTING UILDING 5g6 r 150 t W ti 2C LOCAnM $rn z EXISTING LAME LAT; 42-05-".7 N r c> TOWER LONG& 72-42-18 E W c� ELEV- E27.9 z O .- P �i SURVEY NOTES: ROPeRrr ET7S 1. BASE MAPPING PREPARED BY CLOUGH, HARBOUR do ASSOCIATES LLP FROM A NOVEMBER 1999 FIELD,SURVEY. a a 2. LATITUDE/LONGITUDE/ELEVATIONS WERE OBTAINED UTILIZING ~a LANDS N/�' Q CODE BASED CPS REFERENCED TO NHOOT CPS BASE STATION. NOEL BROWN En LATITUDE/LONGITUDE ARE REFERENCED TO NAD83 MASSACHUSETTS B.3508, P.291 MAINLAND ZONE. COORDINATES SHOWN, IF ANY, ARE EXPRESSED IN U.S. FEET. 'yNp�yy ELEVATIONS ARE REFERENCED TO NGVD 1929. TOP OF STRUCTURE -� HEIGHT AS SHOWN, IF ANY, DETERMINED BY VERTICAL ANGLE OR BY ACTUAL LOCATION. -. •- 3. FOR THIS PROJECT, CLOUGH, HARBOUR & ASSOCIATES LLP USED A TRIMBLE rn rn 0) PATHFINDER 8 CHANNEL PRO XL CPS SYSTEM. TRIMBLE TECHNICAL SPECIFICATIONS STATE A HORIZONTAL DIFFERENTIALLY CORRECTED ACCURACY OF < 1 METER + 10ppm " N FOR THIS SYSTEM, CPS DIFFERENTIALLY CORRECTED VERTICAL ACCURACY IS GENERALLY w- CONSIDERED TO BE 1 1/2 — 2 TIMES THE HORIZONTAL ACCURACY SPECIFICATION, ALL ACCURACIES ARE SITE DEPENDANT. THE ROOF ELEVATION SHOWN, IF ANY, WAS COMPUTED FROM CPS OBSERVATIONS, ALL OTHER ELEVATIONS WERE MEASURED ON SITE AND ARE m �, SITE RELATIVE. m m v 4. NORTH ORIENTATION IS TRUE NORTH BASED ON CPS OBSERVATION. VICINITY PLAN, o MAGNETIC ORIENTATION IS BASED ON WEST SPRINGFIELD MASSACHUSETTS USGS QUAD SHEET. SCALE: 1" = 120� a a 5. UNDERGROUND UTILITIES SHOWN, IF ANY, FROM FIELD LOCATION ONLY. Drawing No. 6. SUBJECT TO ANY STATE OF FACTS THAT AN ACCURATE BOUNDARY SURVEY WOULD DISCLOSE. o� PROPERTY LINES ARE ONLY SHOWN AS APPROXIMATE FROM TAX MAP AND DEED PLOT. GRAPHIC SCALE a' 7. SUBJECT TO ANY STATE OF FACTS THAT AN UP—TO—DATE ABSTRACT OF TITLE WOULD %I DISCLOSE. 120 0 60 120 240 4W a 8. SUBJECT TO ALL RIGHTS, EASEMENTS, COVENANTS OR RESTRICTIONS OF RECORD. 1 z 9. A BOUNDARY SURVEY WAS NOT PERFORMED BY CLOUGH, HARBOUR do IN FEET ASSOCIATES, LLP IN CONJUNCTION WITH THE PREPARATION OF THIS SITE. 1 inch = 120 f1~ 0 5:51:52 GENERAL NOTES: _ $F S— YSTEM SCHEDULE 1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO EXAMINE ALL PLAN SHEETS AND 7. THE CONTRACTOR SHALL COMPLY WITH ALL REQUIRED PERMITS. 9 MECH. a c SPECIFICATIONS AND COORDINATE HIS WORK WITH THE WORK OF ALL OTHER CONTRACTORS TO ENSURE THAT WORK PROGRESSION IS NOT 8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING, AND ANTENNA AZIMUTH M�lSE MODEL �d9 CENTER_(AGL) FEED CABLE SIZE APPROX. CABLE LENGTH COLOR (ACTUAL LENGTH MAY Warr) m INTERRUPTED. INCURRING THE COST OF ALL REQUIRED PERMITS, INSPECTIONS, Rx1A 030 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 19O FT GREEN CERTIFICATES, ETC. TxA 030 ALLGON AWS9016.02D -- 0' 160 FT BOTTOM 1 5/8" 190 FT GREEN/GREEN a ~ 2. THE CONTRACTOR R RESPONSIBLE FOR MAINTAINING I NEAT OFF 9, THE CONTRACTOR SHALL PROTECT EXISTING PROPERTY LINE Rx2A 030 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5 8" 190 FT GREEN/GREEN/GREEN �,ORDERLY SITE, YARD AND GROUNDS. REMOVE AND DISPOSE OFF SITE LITTER AND ALL FOREIGN SUBSTANCES. MONUMENTATION. ANY MONUMENTATION DISTURBED OR / ALL RUBBISH, WASTE MATERIALS, DESTROYED, AS JUDGED BY THE OWNER OR OWNER'S REPRESENTATIVE Rx1B 150 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE m :]-- REMOVE PETRO-CHEMICAL SPILLS, STAINS AND OTHER FOREIGN SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE UNDER THE # 3 DEPOSITS. RAKE GROUNDS TO A SMOOTH EVEN-TEXTURED SURFACE. SUPERVISION OF A LICENSED LAND SURVEYOR. TXB 150 ALLGON AWS9016.02D -- 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE/BLUE THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE- 10. ALL TRENCH EXCAVATION AND ANY REQUIRED SHEETING AND SHORING SHALE BE DONE Rx2B 150 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT BLUE/BLUE/BLUE GROUND STRUCTURES AND/OR UTILITIES BELIEVED TO EXIST IN Rx1C 270 ALLGON AWS9016,02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT WHITE THE WORKING AREA, EXACT LOCATION OF WHICH MAY VARY FROM IN ACCORDANCE OSHA REGULATIONS FOR CONSTRUCTION. - THE LOCATIONS INDICATED. IN PARTICULAR, THE CONTRACTOR TxC 270 ALLGON AWS9016.02D - 0' 160 FT BOTTOM 1 5/8" 190 FT WHITE/WHITE WARNED THAT THE EXACT OR EVEN APPROXIMATE LOCATION OF 11. CONTRACTOR SHALL BE RESPONSIBLE FOR DEWATERING AND THE MAINTENANCE OF Rx2C 270 ALLGON AWS9016.02D NO 0' 160 FT BOTTOM 1 5/8" 190 FT WHIT£/WHITE/YIIHITE SUCH PIPELINES, SUBSURFACE STRUCTURES AND/OR UTILITIES SURFACE DRAINAGE DURING THE COURSE OF WORK. IN THE AREA MAY BE SHOWN OR MAY NOT BE SHOWN; AND IT 12. ALL UTILITY WORK INVOLVING CONNECTIONS TO EXISTING SYSTEMS SHALL BE 16 dBi (14dBd) GAIN 90' HORIZONTAL -2' ELECTRICAL DOWNTILT TMA MODEL # N/A SHALL BE HIS RESPONSIBILITY TO PROCEED WITH GREAT CARE IN COORDINATED WITH THE OWNER OR OWNER'S REPRESENTATIVE AND THE UTILITY OWNER. EXECUTING ANY WORK. 48 HOURS BEFORE YOU DIG, DRILL OR NOTIFY THE OWNER OR OWNER'S REPRESENTATIVE AND THE UTILITY OWNER BLAST. CALL 1-888-DIG-SAFE BEFORE EACH AND EVERY CONNECTION TO EXISTING SYSTEMS IS MADE. z_ 4. THE OWNER OR OWNER'S REPRESENTATIVE SHALL BE NOTIFIED IN WRITING 13. MAINTAIN FLOW FOR ALL EXISTING UTILITIES. OF ANY CONDITIONS THAT VARY FROM THOSE SHOWN ON THE PLANS. o THE CONTRACTOR'S WORK SHALL NOT VARY FROM THE PLANS WITHOUT 14. ALL SITE FILL SHALL MEET SELECTED FILL STANDARDS AS DEFINED BY THE EXPRESSED APPROVAL OF THE OWNER OR OWNER'S REPRESENTATIVE. THE OWNER OR OWNER'S REPRESENTATIVE ON THE DRAWINGS. 0 0 5. THE CONTRACTOR IS INSTRUCTED TO COOPERATE WITH ANY AND 15. CONTRACTOR TO GRADE ALL AREAS ON THE SITE TO PROVIDE POSITIVE DRAINAGE ALL OTHER CONTRACTORS PERFORMING WORK ON THIS JOB SITE AWAY FROM THE BUILDING AND THE TOWER, DURING THE PERFORMANCE OF THIS CONTRACT. N (n a 0 •N THE CONTRACTOR SHALL RESTORE ALL PUBLIC OR PRIVATE PROPERTY DAMAGED OR REMOVED TO AT LEAST AS GOOD OF CONDITION AS BEFORE DISTURBED AS DETERMINED BY THE OWNER OR OWNER'S REPRESENTATIVE. C) v o \ INSTALL mrf wa* AwcR ro GIGWSTRIcnGW, g = > T_ _ REMOW AFTER C0WSMUCnCVV HAS BEEN A-4 v 4) 0 CCUPLE7FD N -+ 07 INSTALL two V V LM/K Cf Q W c) MA rCH EX/SrIN 6 0 z {f) O BAC LARD (M.) A_4 U) w 3 J � � Q —10'X 20'PREFAB EQU/pAomr S1lEL 1FR 1 2 3 ¢ 0- 0 ' �\\ EXISTING PARKING LOT �� / ON L7 V. 6 A8 WE R I GR� A-4 A-4 A-4 a Ld W ` ASPHALT / qs I Z _ \ / INSTALL 6- OF J14" 0TO-SIED � � � J •�-- O t srONE S7/RFAAE m rmmr V? z W = O POLE r / (712 MA rOY EX/S77NO) =o tU 15' f LAVO CABLE TRAY A(0VNTFD �V 4 Ul _ PACE SUPPORM A_4 — 5 m 3 4) F- 0 (f) a WR77CAL G1007AL CABLE RUN A2 3 O WOODS \ GENERATOR \ Q / aW7ER?UNE OF ANMVNAS 70 BE 1 3 + CON c POWER ✓ I- /� PLACM A 160 AGL AV MSANO �- f , J. n 0 / / �, 162.7' LA mac, rowR -- �TELCO — - — — — — — I , EL I Co C AD TOWER HEIGHTS: (I I-- CA Lc) Lo �I N � x2C 030 ! / / / / TOP OF TOWER - 162.7 AGL C W / � TOP PANEL - 147.6 AGL j z F- i ►� GRAVEL i I CASL AY Rx1A1. ' ' SHPANEL 144.5 133.3 AGL AGL O Q 't k 270 TxC X ' I , , DISH 2 - 108.9 AGL m 1 I I Tx «" DISH ISH 4 92.6 AGL Lu a Q r u7 \ I I Rx1C DISH 5 -- 91.7 AGL L (I W EXISTING Rx ❑ a W x I BUILDING l z n ° I �Rx18 U 000 0 EXISTING ACCESS GATE t I . \ / / / / + (1] Z 00 T i� EXISTING GATE I I f / ! , / ❑ m 0 I O ' I I CONC PAD Rx2B W Q -j Z , / / / J Q U I k 150 u�OC�� � -k 1 +z w cl o Oft 4xilaew W � I x x --- x _x _ / / zLLI ---- / J W a �\ � / � w�o m z WOODS �N kj Et7 63 S o WOODS /� �.. MNorrv� POLZ 61 CDa cn 0 , 0)v F N N IN x y, 1 S, m m a in SITE PLAN Ol SCALE: 1" = 10' Drawing No. GRAPHIC SCALE 10 0 6 10 m �0 AM2 IN FEET ) 1 inch - 10 ih IS:51:;6 rn 1. GENERAL 6. CONCRETE (CONT.) o A. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION H. UNLESS INDICATED OTHERWISE ON THE DRAWINGS, REINFORCEMENT SPLICES N SAFETY. SHALL MEET CLASS B, TENSION LAP REQUIREMENTS IN ACCORDANCE WITH ALL B. CONTRACTOR SHALL DETERMINE EXACT LOCATION OF EXISTING UTILITIES PROVISIONS OF ACI 318 LATEST EDITION, UNLESS NOTED OTHERWISE. BEFORE COMMENCING WORK. HE AGREES TO BE FULLY RESPONSIBLE FOR ANY I. CURING COMPOUNDS SHALL CONFORM TO ASTM C-309 a AND ALL DAMAGES WHICH MIGHT BE OCCASIONED BY HIS FAILURE TO EXACTLY THESE DRAWINGS ARE BASED ON INFORMATION PROVIDED TO LOCATE AND PRESERVE UNDERGROUND UTILITIES. CLOUGH, HARBOUR & ASSOCIATES, LLP BY AT&T WIRELESS AND m J. ADMIXTURES SHALL CONFORM ro THE APPROPRIATE ASTM STANDARD As THE TOWER OWNER, AT&T WIRELESS AND THE TOWER OWNER C. INCORRECTLY FABRICATED, DAMAGED, OR OTHERWISE MISFITTING OR REFERENCED IN ACI-301, o NONCONFORMING MATERIALS OR CONDITIONS SHALL BE REPORTED TO THE OWNER K. DO NOT WELD OR TACKWELD REINFORCING STEEL. ASSUME ALL LIABILITY FOR ALL STRUCTURAL ANALYSIS, INTEGRITY PRIOR TO REMEDIAL OR CORRECTIVE ACTION. ANY SUCH ACTION SHALL AND REQUIRED IMPROVEMENTS OF AND TO THE EXISTING TOWER, REQUIRE APPROVAL, L. ALL DOWELS, ANCHOR BOLTS, EMBEDDED STEEL, ELECTRICAL CONDUITS, PIPE EXISTING STRUCTURES, AND EXISTING SUPPORTS. SLEEVES, PIPING, WATERSTOPS, INSERTS, GROUNDS AND ALL OTHER EMBEDDED D. EACH CONTRACTOR SHALL COOPERATE WITH THE OWNER'S REPRESENTATIVE, AND ITEMS AND FORMED DETAILS SHALL BE IN PLACE BEFORE START OF CONCRETE COORDINATE HIS WORK WITH THE WORK OF OTHERS, PLACEMENT. E. PAINT ALL ANTENNAS, MOUNTING HARDWARE, CABLES, CABLE TRAYS, ETC. TO MATCH M. LOCATE ADDITIONAL CONSTRUCTION JOINTS REQUIRED TO FACILITATE EXISTING STRUCTURE PER OWNER REQUIREMENTS. OWNER SHALL APPROVE COLOR. CONSTRUCTION AS ACCEPTABLE TO ENGINEER, PLACE REINFORCEMENT CONTINUOUSLY THROUGH JOINT, F. ALL DAMAGED, MARRED, SCRAPED, ABRADED, ETC. AREAS OF EXISTING PAINT SHALL BE N. REINFORCEMENT SHALL BE COLD BENT WHENEVER BENDING IS REQUIRED, z REPAIRED PER OWNERS REQUIREMENTS. OWNER SHALL APPROVE COLOR. I r 0, PLACE CONCRETE IN A UNIFORM MANNER TO PREVENT THE FORMATION OF COLD 2. DESIGN LOADS JOINTS AND OTHER PLANES OF WEAKNESS. VIBRATE THE CONCRETE TO FULLY II 1 0 A. WIND LOADS: PER THE STATE BUILDING CODE EMBED REINFORCING. DO NOT USE VIBRATORS TO TRANSPORT CONCRETE THROUGH z B. PRESUMPTIVE BEARING CAPACITY: 2000 PSF CHUTES OR FORMWORK. \ (VERIFY SOIL BEARING CAPACITY WITH GEOTECHNICAL ENGINEERS REPORT) 0 C. PREFABRICATED BUILDING: 40,000 LBS P. DO NOT PLACE CONCRETE IN WATER, ICE, OR ON FROZEN GROUND. CENTERLINE OF ANTENNAS TO BE D. ROOF UNIFORM SNOW LOAD: 40 PSF PLACED AT 160 AGL ON EXISTING N z (DRIFTED SNOW AS PER THE STATE BUILDING CODE.) Q. DO NOT ALLOW CONCRETE SUBBASE TO FREEZE DURING CONCRETE CURING AND \ 163' LATTICE TOWER N o SETTING PERIOD, OR FOR A MINIMUM OF 14 DAYS AFTER PLACEMENT. II . II � " 3. EXCAVATIONS/FOUNDATION I EXISTING PANEL ANTENNAS ® 146' AGL � R. FOR COLD-WEATHER AND HOT-WEATHER CONCRETE PLACEMENT, CONFORM TO A. FOUNDATION EXCAVATION SHALL BE HAND-TRIMMED TO REMOVE LOOSE APPLICABLE ACI CODES AND RECOMMENDATIONS, IN EITHER CASE, MATERIALS MATERIALS. CONTAINING CHLORIDE, CALCIUM, SALTS, ETC. SHALL NOT BE USED. PROTECT B. EXTERIOR FOUNDATION BACKFILL SHALL BE SELECTED GRANULAR FILL. FRESH CONCRETE FROM WEATHER FOR 7 DAYS MINIMUM. V) W O C. DO NOT PLACE FOOTINGS IN WATER OR ON FROZEN GROUND. U_ J O EXISTING 6' DISH 0 133.3' AGL D. SOIL BEARING SURFACES, PREVIOUSLY ACCEPTED BY GEOTECHNICAL ENGINEER, 6� 030` WHICH ARE ALLOWED TO BECOME SATURATED, FROZEN OR DISTURBED SHALL BE �' H- a 10 W REWORKED TO SATISFACTION OF GEOTECHNICAL ENGINEER. < W cV E. DO NOT ALLOW GROUND BENEATH FOOTINGS TO FREEZE, O Z Z F. FOOTING EXCAVATIONS SHALL BE CUT NEAT. 6`0+ �� * 0 3 Z .j Q 00 0 w N L G. ALL STRUCTURAL BACKFILL AND SUBBASE UNDER SLABS-ON-GRADE AND FOOTINGS ANTENNA MOUNTING PIPE \, M ¢ z W SHALL BE SW" OR BETTER PER ASTM D-2487 COMPACTED TO A MINIMUM 95% BY MICROFLECT PART NO. STANDARD PROCTOR DENSITY PER ASTM D-698. B1478 ~ W z: O 0 H. SUBGRADE BELOW SLAB-ON-GRADE SHALL BE REVIEWED AND ACCEPTED BY U8 EXISTING 8' DISH 0 112' AGL EXISTING 6' DISH ® 108.9' AGL o � 3 GEOTECHNICAL ENGINEER BEFORE CONCRETE SLAB PLACEMENT. SAG N a �, 2 m � 4. ANTENNA SUPPORT BRACKET NOTES N z �''� 5 W m O � w & A. DESIGN RESPONSIBILITY OF ANTENNA MOUNTING BRACKETS AND POLES AND ALL z COMPONENTS THERE OF AND ATTACHMENT THERE TO SHALL BE THE RESPONSIBILITY 27Q{� �� a 0 OF THE MANUFACTURER. MFR SHALL PROVIDE: TO THE ENGINEER FOR APPROVAL, 14 in �3 o 0 DRAWINGS DETAILING ALL COMPONENTS OF THE ASSEMBLY, INCLUDING CONNECTIONS, ® a ¢ DESIGN LOADS, AND ALL OTHER PERTINENT DATA. U, o N FUTURE PANEL ANTENNAS STANDOFF FRAME BY z � B. BRACKETS SHALL BE DESIGNED TO SUPPORT CURRENT AND U MICROFLECT PART NO. AND COAXIAL CABLES AS SHOWN. 995fi0) OR EQUAL z Of EXISTING 4' DISH 91,7' AGL -� EXISTING DISH 8' CAD 92.6' AGL 5, STRUCTURAL STEEL NOTES o 150 R (� 0 0 " � o aca � � N � A. STRUCTURAL STEEL SHALL CONFORM TO THE LATEST EDITION OF. THE AISC SPECIFICATION o w ""� W I FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS". ~ o O J Q I B. STEEL ANGLES, BASE PLATES, BEARING PLATES AND MISC. FABRICATION SHALL BE MADE 1 Y FROM STEEL MEETING THE REQUIREMENTS OF ASTM-A36 WITH A MINIMUM YIELD STRESS _ NO SCALE a_ /� m U� a O co OF 36 KSI, ALL STEEL TUBES AND PIPES SHALL BE A500 STEEL MINIMUM, EXISTING 163' LATTICE TOWER UJ Q � C. ALL INTERIOR STRUCTURAL STEEL SHALL BE, WHEN DELIVERED, FINISHED WITH ONE COAT u" W w FABRICATORS NON-LEAD RED OXIDE PRIMER, PRIMING SHALL BE PERFORMED AFTER SHOP FABRICATION TO THE GREATEST EXTENT POSSIBLE. ALL DINGS, SCRAPES, MARS, Q Q >` Q z AND WELDS IN THE FINISHED AREAS SHALL BE REPAIRED BY FIELD TOUCH-UP PRIOR / _ ..■. U TO COMPLETION OF THE WORK. - r 11 0 Q D. ALL EXTERIOR STRUCTURAL STEEL SHALL BE, WHEN DELIVERED, HOT-DIP GALVANIZED MICROFLECT PART #B251 V °z ACCORDING TO ASTM A123. TOUCH-UP FIELD WELDS AND ABRADED AREAS W/2 COATS COMBINATION SQUARE = O Ul m OF GALVANIZED PAINT. RAIL �/ UJ , 1111 . E. DO NOT PLACE HOLES THROUGH STRUCTURAL STEEL MEMBERS EXCEPT AS SHOWN AND W I DETAILED ON STRUCTURAL DRAWINGS. ` z F. CONNECTIONS: Q z 1. ALL WELDING SHALL BE DONE BY A CERTIFIED WELDER USING E70XX ELECTRODES J uj AND WELDING SHALL CONFORM TO AISC AND AWS D1.1. WHERE FILLET WELD SIZES W 0 U ARE NOT SHOWN, PROVIDE THE MINIMUM SIZE PER TABLE J2.4 IN THE AISC "MANUAL cj� OF STEEL CONSTRUCTION ", 9TH EDITION. AT THE COMPLETION OF WELDING, ALL U DAMAGE TO GALVANIZED COATING SHALL BE REPAIRED. _ V) 2. MINIMUM CAPACITY OF CONNECTIONS: FOR CONNECTIONS NOT DETAILED, - w PROVIDE CONNECTION CAPACITY OF AT LEAST THAT REQUIRED BY PART 2 OF THE 0. AISC MANUAL (9TH EDITION) IN THE SECTION "ALLOWABLE LOADS ON BEAMS", FOR THE GIVEN MEMBER AND STEEL SPECIFICATIONS. CONCENTRATED LOADS NEAR SUPPORTS MUST BE ADDED. 3. CONNECTION DESIGN BY FABRICATOR WILL BE SUBJECT TO REVIEW AND APPROVAL 5' f LONG CABLE TRAY MOUNTED ON n BOLTED HALL USE BEARING TYPE GALVANIZED ASTM A325 BOLTS 3 4" DIA. POLE SUPPORTS. 4. BOL DS ( / } AND SHALL HAVE A MINIMUM OF TWO BOLTS UNLESS NOTED OTHERWISE. 10' X 20' PREFAB EQUIPMENT SHELTER 5, NON-STRUCTURAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8" DIA, GALVANIZED ASTM MICROFLECT PARTE8291 ` ON A 11 X 21' CONCRETE SLAB WITH A307 BOLTS UNLESS NOTED OTHERWISE. CROSS PIECE 40 LONG \� TOP ELEV. fi" ABOVE FINISH GRADE Errs GALV VERTICAL SPACING \ �* 6. CONCRETE PER MFR RECOMMENDATIONS—.,, EXISTING EQUIPMENT BUILDING A. DESIGN AND CONSTRUCTION OF ALL CONCRETE ELEMENTS SHALL CONFORM TO INSTALL 8' HIGH CHAIN � THE LATEST EDITIONS OF THE FOLLOWING APPLICABLE CODES: ACI 301 CHAIN LINK FENCE WITH BARBED r EXISTING CN LINK FENCE �I "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS"; ACI 318, / WIRE (TO MATCH EXISTING) x "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE"; MNp�w x x B. MIX DESIGN SHALL BE APPROVED BY OWNER'S REPRESENTATIVE PRIOR TO PLACING CONCRETE. C. CONCRETE SHALL BE NORMAL WEIGHT, 6% AIR ENTRAINED (t1.5%) WITH A MAXIMUM m rn m W 4" SLUMP, AND HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 4000 PSI o ti UNLESS OTHERWISE NOTED. n N O N N D. MAXIMUM AGGREGATE SIZE SHALL BE 1 E. THE FOLLOWING MATERIALS SHALL BE USED; -� I �_ I-- - I - 1 -i I =W- : �11 1�� II-1� 1-1`:;' I�� €1LI-� - i- IT1�LI 1 I —IJ=I�11 �11 p PORTLAND CEMENT. ASTM C 150 TYPE I �� I- 111- = 11=111-��LI- I m m i :!ll—UI=Lu ,I I "' ��� a m o REINFORCEMENT: ASTM A 185 i�- II—III- III—IfI—III-+II- tt II I- I' ' III II,;II , IIjf-J�-J� tJ� II II IP Y NORMAL WEIGHT AGGREGATE: ASTM C 33 III--III Pm �, o ;u WATER: DRINKABLE a 0 r L] O U ADMIXTURES: NON-CHLORIDE CONTAINING Drawing No. F. REINFORCING SHALL CONFORM TO ASTM A-615 WITH SUPPLEMENT. MINIMUM 3 YIELD STRENGTH Fy = 60 KSI. REINFORCING DETAILS SHALL BE IN 2 CABLE SUPPORT ON ANTENNA TOWER _ NO SCALE ACCORDANCE WITH THE LATEST EDITION OF ACI 315, G. CONCRETE COVER AROUND REINFORCING BARS U.N.O. SHALL BE: - NO SCALE { ) NOTES 1. CONTRACTOR SHALL COORDINATE EXACT ANTENNA ATTACHMENT. AIIIII=31. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED EARTH........3.0 NOTE: CONTRACTOR SHALL VERIFY CABLE MOUNTING W/STRUCTURAL 2. ANTENNAS TO BE INSTALLED WITH DOWNTILT BRACKETS, 2. CONCRETE EXPOSED TO EARTH, WEATHER.........................2" ANALYSIS RECOMMENDATIONS. 3. SLABS....................................................3/4" 4. ALL OTHER CONCRETE.....................................1 1/2" 15:51:OS rn v \ o � Q N 5, m a � a a in CONIC CAP a 3/4" DIA. A325N 6" DIA SCHED 40 STEEL L_ — J ! ANCHOR BOLTS PIPE FILLED W/LEAN CONC MID) I E 14'x21' CONC SLAB z 3 SHELTER 1/a n BASE FRAME is i . Z BM FLANGE I ll\�PL 12"x12" 1/2" EXPANSION 3" 6" FILLER & SEALANT f 1 I 0 c Z o z O T/STL = T/CONC SHELTER BEARING PLATE (TYP} I i ANCHOR BOLT 10 x2D SHELTER \ v .+ Q M SEE SLAB ,� (TYP) /\�,✓\\ \\�/ v a 2' SQ, CONCRETE PAD W TYP ���� a 4 ' 4 \\/\\\ , UNDERBC CONC PAD.ASE _ < Q - m TYP 3/16 \i� O ¢ LiJ N 8'-6" 8'-6" 1'-6" 4 e Q O YI O (TYP) El BEASNQ eLATE DETAILas NO SCALE a 0 d .L Q � a � y Q � NOTE: CONTRACTOR SHALL VERIFY SHELTER BASE W FRAME CONSTRUCTION PRIOR TO WELDING .mod A . Z Q J 0 TO BEARING PLATES, Lu A 4 " CONC BASE z -j = O 1 d (3000 PSI CONC) � o W SHELIER PLAN VIEWNO SCALE as 'A 4 z U W 0 4 �"' O �c v 4 (!� 0 m a Q 1'-Ir DIA. � QUI �I o °O Ln jW N It � J � BOLLARD DETAIL J Q zESNO SCALE OLn m r� Y Woo0 ' Q W ErW 3 Q �- [] Iq- z FENCE CAP Q W Q � > M 00 CABLE TRAY R (IQ d = Q � 00 z m Z GRIP STRUT Q o 3/8" DIA THREADED ROD �n � W SNAP-IN HANGER FOR V+ Z = COAX CABLE (TYP) �a 0 z 3 ROWS OF GALV J W P1000 UNISTRUT 3" DIA SCH 40 U PROPOSED SHELTER PIPE COLUMN FOR WAVEGUIDE SUPPORT 1" CHAMFER #4012" EW w 3: � � z (TYP ALL SIDES) 6" CONCRETE SLAB 6" EXPOSED a CONCRETE 2" CLR CONCRETE u - PIPE BASE 2x4 STAKE 5' O.C. EXISTING AND PROPOSED U Errs b FINISH GRADE mil POLY ON �vpa•ra4��nq��go�gquagq�nqoti� o Uyq titiq UNDISTURBED SUBGRADE FINISHED GRADE ORp 00000 q00 pgggOqqqqqq0q°°q00qq Oqq q°q q°� Q00-0000 0000 000000 4 gaoaO4ogoapo°00000,og000000000000000 0 STAPLE THROUGH NYLON 0000 000 O00 Oq4 qq0°0 qq0 ggOgqqq4qOqqqO°gOgapg04qqqpOqO , O� WASHER, 2 PER STAKE ¢, r o \ TRENCH, LAY FABRIC SUPAC OR MIRAFI FILTER U. ``/// ` AND BACKFILL. S» FABRIC y b SO / �/\\\ 0MNoyrW EXISTING GROUND -� 6" CRUSHED STONE (MIN,) I IEI I El I I I I_l I I_l I I_I 1 I-I I -� I I-III-III ,�. w- I-III I I Ed I I-1 11-I xI $" I=III=III=111-� UNDISTURBED SUBGRADE (BEDROCK OR , I =1 I I=III 1 I 1 11 I 1 I 11, ,1 11 l l I;, l , N N ' STRUCTURAL FILL) r T w Q 2'-0" a WIRE 51 in 3 STAPLE NO SCALE 1'-0" DIA 40 NOTES: 1. PROVIDE CORNER BARS AT EACH CORNER OF PAD, a o BAR SIZE SHALL MATCH HORIZONTAL REINF. 4 CAB TRAY5 Drawing No. i+ 2. COORDINATE LOCATION OF UTILITY PENETRATION THRU SILT FENCE DETAIL SHELTER SLAB WITH ELECTRICAL DRAWINGS. _ NO SCALE - NO SCALE 3, CONTRACTOR SHALL WATER STOP ALL CONDUIT NOTE: ICE BRIDGE SHALL SPAN NO MORE THAN 6 -D PENETRATIONS THRU SLAB AND SHELTER, BETWEEN SUPPORTS, Am4 4, COORDINATE SLAB PLAN W/ SHELTER MFR. Z J 14 n 13:30:36 rn O 0 TRUE U TlL[TY_C0TACTSi LEGEND N WESTERN MASS ELECTRIC CO. ► ' • RICK RIZZLIE — — — — � — UNDERGROUND CONDUIT a C) � {413} 785-5871CL ---------- #2 AWG GROUNDING CONDUCTOR 140 3 METER o 1 1 GROUND BAR ��- J , -''� \` W %� j Q 5/8" x 10'-0" COPPER CLAD GROUND ROD. MINIMUM SPACING 10'-0", o �`• i , MAXIMUM SPACING 15'-0" EXISTING METALLIC FENCE & NEW co INDICATES CODED NOTE NUMBER 3 cn R j 12 ��i 1 DETAIL NUMBER a 1 AT&T PREFAB E-2 DRAWING NUMBER LOCATION 0Of i E.QUIPMENT CL r U i SHELTER . r n i V? In Fn 1 5 1 E^2 1. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM CONDUCTORS SHALL NOT BE USED. 2. CAP ALL EMPTY CONDUITS AT BOTH ENDS. SEAL ALL CONDUITS WITH PULL CORDS & W 1 6 E-3 ` CONDUITS WITH GROUND WIRES. Y V O 1 3. COORDINATE ALL PENETRATION LOCATIONS WITH ACTUAL BUILDING PLANS. U_ N 0 j 4. DRAWINGS WERE COMPLETED BEFORE UTILITIES COULD CONFIRM SOURCE OF SERVICES. v Z EU O 1 DRAWINGS ARE BASED UPON SITE OBSERVATIONS ONLY. J It , 0 i a W ) 1 CONC PAD 1 r \ O � O r ' i U} W . 3 a ~ N 10 ;\ \\ � i +•� r � E-3 TYP. �` � J Q y � Q ��w U J — 0 \ r; cn Z W = 0 Z LL.I 0 N CABLE TRAY \`'�� \ \\\�`�` LI1 0 `j m U) a � � Ln o a 0. N Ln C4 ' 8 E-3 ��' z O QI � � ai 00 LLWffW � ENLARGED EQUIPMENT AREA — GROUNDING PLA Q a z SCALE: 3/8" -� Za > 00 �/ o z � °� m z 4 < Q r 11 E-2 r W J nEr 0 W (� a` _ ] W Z U _ ❑ az 3 r, _ _ LLJ f � LLJ 13 5 0Q z / E-3 Z CODED NOTES % ~ ~ � � � • O1 4" C. w/(3) 600 KCM. x � 2"C/ w 3 #4/0 + #6G TO BUILDING DISTRIBUTION SYSTEM. COORDINATE ` • • EXACT �RMINATION LOCATION WITH OWNER, X P�U ET7S& O 4" TELEPHONE CONDUIT WITH PULL WIRE. I ' O4 TELEPHONE SERVICE ENTRANCE. PROVIDE 4" CONDUIT w/ PULL WIRE CONC W/ 2 F b TO BUILDING TELEPHONE BACKBOARD. COORDINATE EXACT TERMINATION LOCATION WITH OWNER. GENERATOR AT&T PREFAB, `J a� EQUIPMENT Na O5 EXTERIOR GROUND RING. SHELIER np. i O BUILDING MOUNTED GROUND BAR. CONC a 2 rn rn rn O TOWER MOUNTED GROUND BAR. ' 8 4 ANTENNA GROUND BAR. 4 o N n N O CONNECTION FROM EXTERIOR GROUND RING TO INTERIOR HALO. 3 10 CONNECT TO EXISTING EXTERIOR GROUND RING. LOCATE IN FIELD. m m 11 EXISTING UTILITY POLE WITH ELECTRIC AND TELEPHONE SERVICES X CONC PAD 0° o FOR AT&T. v v t W 12 HVAC UNIT. In IF 1 0 SQUARE "D" METER-PAK METER CENTER w 13 NEW 400A, 120/240V, Drawing No. MI 2 METERS. (1) 200A METER SOCKET/CB FOR AT&T AND (1) 200A M TER X SOCKET/CB FOR FUTURE. METER BY UTILITY. ccCC l - E-1 W PARTIAL SITE POWER R TELEPHONE PLAN `= SCALE: 1/4" = 1'-0" J C1 a 15:50:71 0 6 ca TIE INTO EXISTING TIE INTO EXISTING EXTERIOR GROUND RING EXTERIOR GROUND RING M M LOCATE IN FIELD LOCATE IN FIELD fl U in, I I a o Q EXTERIOR GROUND RING WITH GROUND RODS AS INDICATED ON GROUNDING PLAN J- ---..--�--__ UNDERGROUND UTILITY cn ww.ar--T—Lr--w�rirrrr—rw-----�.. --- --- ►—.. — —r r-----r----- --------- —.rwwawr�rrrrw wrrrrr:..��wr--rwrr�.wrw..r I 1 I i I 1 I j BACKFLL WARNING TAPE I 1 I j j j j j j SEE NOTE FINISHED GRADE rn co CIO I ! I 1 I I I TOWER GROUND BAR \ INTERIOR HALO j HVAC TELEPHONE j FENCE POST EXISTING CABLE TRAY I 1 \ \/ z r 4 PLACES I EQUIPMENT AC SERVICE SERVICE I OPP. CORNERS FENCE &SUPPORTS I 1 \ Q V) TYP, 2 TYP. 2 i i + < TELECOMMUNICATION CABLE TRAY M o a CABLE SHEATH SAW CUT EDGE EACH ,- SIDE (IF REQUIRED) TLIJ J \ 1 3" SAND ENVELOPE ➢' "as. .; .l 4..,,:r; ONE OR TWO CONDUITS o "' SURROUNDING ! I I CONDUIT .-' ;, :,,,- AS REQUIRED. SEE SITE 0 Li PLANS. F 1 I 3" BUILDING GROUND BAR 12" I MASTER GROUND BAR ANTENNA GROUND BAR (TYP, OF 3) NOTE: REPLACE EXISTING SURFACE CONDITIONS IN KIND TO INCLUDE, BUT NOT LIMITED TO: CONCRETE, CRUSHED STONE, SELECT W j O GRAVEL, ASPHALT CONCRETE, TOPSOIL AND GRASS, TELECOMMUNICATION CABLE TRAY U N O CABLE SHEATH CABLE TRAY 1 PLACE ANTENNA TELECOMMUNICATION CABLE=TRAY FRAME CABLE SHEATH 0 Q) 2 UNDERGROUND CONDUITS a J � rn NO SCALE D W C O w N O N!QIEL CONNECTION TYPE TO EQUIPMENT AND GROUND BARS SHALL BE COORDINATED WITH EQUIPMENT MANUFACTURER AND OWNER, w . . ¢00 .> Q AND z W IZ � NJ 0 5/$" x 10'-0" COPPER CLAD GROUND ROD, ? U W = O ------ 2 AWG BARE SOLID TINNED COPPER GROUND WIRE. W W # p J :3 V) 5 W m N -�-- #6 AWG BARE SOLID TINNED COPPER GROUND WIRE, LLJ 0 Or GROUND BAR o 0 It -------- #4/0 AWG FLEXIBLE COPPER BRAID Q a 1 SCHEMATIC DIAGRAM -- GROUNDING SYSTEM Q a � � N � NO SCALE W N It JQI O _j QWEEW 3: Q ~ 00- w UTILITY POLE }Q Q z n U o0 BARBED WIRE CRIMP-ON CONNECTOR W r ' Z 0000 TO EACH STRAND (TYP,) (j 0 m z6 IO HEAVY DUTY EXOTHERMIC rn J TOP RAIL WELD {J, W I a 2 2 ] � z ° aNOTES s z U FENCE FABRIC J W 1. BOND ALL METAL OBJECTS TO POLE GROUNDING SYSTEM. r W U 2. COORDINATE ALL INSTALLATIONS TO UTILITY POLE WITH UTILITY COMPANY, Ln U 1 POLE CQDED NOTES In w 4 CONDUCTORS FROM UTILITY POLE TO METER INSTALLED BY CONTRACTOR. Z O CONTRACTOR TO PROVIDE SUFFICIENT CABLE TO REACH A MINIMUM OF 24" �O z ABOVE TERMINATION LOCATIONS, AND ROUTE TO SERVICE DISCONNECT WITH- z o OUT A SPLICE o O PROVIDE INSULATING BUSHING. USE DUCT SEAL TO MAKE WATERTIGHT. u 3 3 3O PIPE STRAPS, INSTALL AT NOT MORE THAN 2`--0" INTERVALS, TELEPHONE SERVICE CONDUIT WITH PULL CORD. SEE SITE PLAN FOR CONDUIT N� ExrS d c FENCE POST SOLID TINED N GROUND O SIZE do ROUTING, �� �� v) OUN WIRE FINISHED O SWEEPS MUST BE MADE USING RIGID GALVANIZED STEEL CONDUITS. U. GRADE Y17 TENSION WIRE HEAVY DUTY EXOTHERMIC WELD WITH CORROSION PROTECTION j g rn v rn rrn --� EXTERIOR GROUND RING 5 _ TYP, I TO EQUIPMENT r SEE ELECTRICAL PLAN I FOR CONTINUATION a I { 30" OR 6" BELOW FROST LINE m I a I x I I x °° I m m v 3 FENCE GROUNDING 4 SERVICE POLE — POWER & TELEPHONE o o M _ NO SCALE -•-- NO SCALE Drawing No. co 1 a m a m L Em2 z z w J V O 15:49:50 0 0 o a \ m v a U CO 3/4" 1-3 4.. 1.. 1.-�.. o TYP, TYP. TYP. o a o � 3/4" 1--3 4' 1" 1-1 2" TYP. TYP, ITYP.1 7/16"O HOLE (42) o O x cv 0 0 + 0 0o+ 0 o+ 00 0 0— - 7/16 HOLE (16} 000000000000E) + 6 F r � 00000— _ N � 00000000000000-- - - - N � � - _ -0000000^ 2 - 2 7/16"0 MOUNTING HOLE l 0 7/16"0 MOUNTING NG HOLE 1 (2) 3 0 3 O LO w 0 SIDE VIEW PLAN VIEW o W SIDE VIEW P L A N , V I E W a O #R415DA4 INSULATOR #WBKT1 WALL BRACKET #GBI1441BERMGB 01 #R415OA4 INSULATOR O #YJBKTI WALL BRACKET o3 #G6114212ERSG6 1 GROUND BAR ASSEMBLY 2 T W GROUND BA NO SCALE R ASSEMBLY (SECTOR) o v W (� O _ NO SCALE ? �-- NQ� 1. ALL PARTS REFERENCED MANUFACTURED BY HARGER LIGHTNING PROTECTION, INC. _ ¢ _j N O NOTE: 1, ALL PARTS REFERENCED MANUFACTURED BY HARGER LIGHTNING PROTECTION, INC. F-- a W p C) F- y � N O (n Q Ld a3 . . . J N � a od a Q y W 0 � W = 0 - 5 U 3 m J Z3 U) I w] 5 Li.1 m N W 0 F- a � O HEAVY DUTY EXOTHERMIC WELD a FENCE POST SOLID TINNED GROUND WIRE u� o o o ]TENSION WIRE Li J U N JzI HEAVY DUTY EXOTHERMIC WELD a p I WITH CORROSION PROTECTION m Q °0 LUtiY EXTERIOR GROUND RING Q 11 W 3 r. 00 30" OR 6" BELOW FROST LINE EXTERIOR SHELTER [ Q Q a00a WALL ' U J Z ID z J 3 EXISTING FENCE - GROUNDING J NO SCALE W (A a� ` � W z i 0 < 0 rT J W W W A A SQUARE _j U r 1..1 � METER- U PAK MP42200 $ � Z GRADE B B0 ZO GROUND RING - o HEAVY DUTY �v erTS erg EXOTHERMIC o WELD s o D � a y a N % PCul FINISHED QW GRAD£ Qrvvr a �C o 30" OR 6" BELOW FROST LINE .�w 0 0 a 0 a 0 0 0 2"C. PVC TO AT&T PRE-FAB SHELTER 4" PVC FROM UTILITY 4 COPPER—CLAD STEEL 4 O GROUND ROD in, NO SCALE 57 METERBANK — ELEVATION c m ' a y , N 0 SCALE 0 } Q N c� r W O d I M Drawing Na. co MJ1I N n` °0 i w S Z w a 3 O 15:49:V ' rn rn u \ � o � o � 04 N N r m a � � a � � 4 Q m a a p 0 co Z T& T 1/-.,J J SS SL R v] c Al S O U rn O) N C \ U N SOUTHIVICK S11TE I , D , # SP 38M Z_ � z p Z U O � F- W U a_ D � a � w V) yr C Z j O W ATOP PROVIN AOUNTAINar . . . . . . . Y � V c A (; AViA1M NIASSA (; HUSETTS L _ o c V W � 0 � N � o 1J) w • • 3 TITLE Q � W o � D 0 DRAWING N0. _ W N I I--- J — -o v tidee ad � o a LQ, T--1 TITLE cn z W = o o a� I A-1 VICINITY PLAN o o 0011wo A--2 SITE PLAN o En a �r A-3 TOWER & ANTENNA DETAILS _� a- � o S 4ah 0 A= a A-4 MISCELLANEOUS DETAILS 0 of � DIRECTIONS TO SITE: fi" Q q= z E-1 ELECTRICAL SITE PLANS Q TAKE THE MASS PIKE WEST TO EXIT 3. TAKE RIGHT ONTO � o� z b �' � Q E-2 ELECTRICAL DETAILS R joins 3r 3 b fn o � 202/20 SOUTH THROUGH WF�W. TFIELD INTO SOUTH WICK. FOLLOW �r +1E-3 ELECTRICAL DETAILS 202/20 TO JCT 57 (FEEDINGS HILL ROAD), TAKE LEFT ONTO 3 p U] o ° RTE. 57 (EAST) INTO AGAWAM. AFTER ENTERING AGAWAM TURN LEFT o s Q 0. �- N to ONTO NORTH WEST STREET. FOLLOW NORTH . WEST STREET TO RADIO STATION a J W U SIGN 0 J z W ,( N LEFT) TURN LEFT IN 7 0 DRIVE AND FOLLOW TO BACK OF BUILDING. z : Z z Y LATTICE TOWER LOCATED DOWN BEHIND RADIO STATION BUILDING. f , Mtn a Lj o CO LLWaWa >- ' � LO w Q ~ ° QZ North j U }� cc � S t (� z 00 ARaEcrI 3 U ❑ Q ` n anglewood Lane ; rn z m � QU�1Q Q z r� .s� o U� � � I c0 Mountain �1, ] LOz 0 < 0 J z Ld 0W U U il�_ 9 U U) 0 p' W r I C' p � Z L) LQCATI ON M„AP '° 3: ,SITE STATISTICS: NO SCALE U O �I J UNDERLYING LANDOWNER: ADAMS TV OF SPRINGFIELD INC. Q U N ZONING DISTRICT: AGRICULTURAL p a a LATITUDE: N-42'05'01 ,7" O CONSTRUCTION DOCUMENT APPROVAL DATE LONGITUDE: W-72042'15.8"(GPS — NAD83) N ci X GROUND ELEVATION AT }- BASE OF TOWER: 627.9' (GPS NGVD29) Q RF ENGINEER BY: — TYPE SITE: EXISTING TOWER Z Q W d O U AT&T CONSTRUCTION COORDINATOR BY: JANUARY 12, 2000 s H -~ Fn SITE ACQUISITION COORDINATOR 8Y: C CLOUGHe HAR B0 (,, R Drawing No. & ASSOCIATES LLP " a #� ERICSSON CONSTRUCTION/RBS: MANNO COPY GHT ENGINgo EERS, SURVEYORS, 5 a svli Z III WINNERS CIRCLE — ALBANY, NEW YORK — 12205 T�l +� P.O. BOX 5269 518-453-4500 . a UNDERLYING LANDOWNER BY: oav:-I: Y-155 01/14/2040 MZ4:09